Review Stop FUEL
Sequence Number 1
Notes
Date Text
2006-10-17 13:39:28DENIED:
 PLEASE CLARIFY MANUFACTURE'SSUBMITTAL DATA, TWO
 DIFFERENT GENERATOR'S WERE SUBMITTED.ONE IS
 INDICATING NATURAL GAS OR LP AND THE SECOND GENERATOR
 IS A DIESEL GENERATOR.PLANS ALSO INDICATE DIESEL
 GENERATOR.
  
 1.FOR THE DIESEL GENERATOR PLEASE CLARIFY IF THIS
 WILL HAVE A SUB-BASE SELF CONTAINED FUEL TANK OR REMOTE
 FILL/ DAY TANK.
  
 2.PLEASE PROVIDE ANY FUEL PIPING, SIZE, MATERIAL OR
 LAYOUT IF APPLICABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].