2006-10-13 15:45:39*****DENIED*****
  
  
  
 1.)IN THE EVENT OF A FUEL LEAK, HOW WILL THE RUNOFF
 BE CONTAINED TO NOT COMPROMISE LIFE SAFETY AND/OR THE
 ENVIRONMENT?
  
  
 2.)LOCATION OF STRUCTURE SHALL NOT HINDER, IMPEDE, OR
 OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF.
  
 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL
 (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE
 ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH,
 AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE
 LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6).
  
 4.)WHAT IS THE FIRE RATING OF THE ROOF?
  
 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE
 DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE
 AIR?
  
  
  
  