Plan Review Notes
Plan Review Notes For Permit 06080393
Permit Number 06080393
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-25 00:00:00REVIEW IN PROGRESS
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE OWNER AND PERMITTING
 OF UNIT MAY NOT BE ASSIGNED OR ADRESSED
 TO THE OWNER OF ONE OF THE FEE SIMPLE
 UNITS. PLEASE SEE PERMIT APPLICATION HAS
 THE GENERATOR BEING PERMITTED TO UNIT
 H1713, AND OWNER BEING CAROL WEBSTER
 WHICH IS THE OWNER OF UNTI #1013. IT WAS
 LOCATED ON THE PAPERWORK THAT SHE IS THE
 PRESIDENT OF THE ASSOCIATION HOWEVER THE
 GEN CAN NOT PERMITTED TO HER ADDRESS.
 PLEASE ADJUST PERMIT APPLICATION, AND
 PAPERWORK.
  
 2) NOTE: PLEASE CORRELATE GENERATOR
 SPECS, PLANS AND PERMIT APPLICATION.
 PLEASE SEE SPECS FOR NATURAL GAS, AND
 PLANS FOR DIESEL. ?
 106.1.2 FBC
  
 3) NOTE: PLEASE SEE PLANS STILL SHOW
 LEAVING THE MTS DEVICE IN LOCATION, IF
 THIS ISLEGALLY REQUIRED BACK UP
 SYSTEM, AN AUTOMATIC MEANS OF TRANSFER
 OF POWER MUST BE IN PLACE. THE
 RECEPT/MTS MAY REMAIN, HOWEVER THIS
 SHOULD BE WIRED IN THE EVENT OF FAILURE
 OF THE GEN, THEN A PORTABLE CAN BE USED.
  
 4) NOTE: PLEASE SEE IF ELEVATION IS 6.5'
 AND BFE IS 7.0, THE 8" SLAB IS ONLY 2"
 ABOVE BFE, WHERE IT WOULD BE REQUIRED TO
 BE 6" ABOVE BFE, PLEASE ADJUST.
 NFPA-110 7.2
  
 5) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS FOR SAID LOADS WHICH WILL
 BE IMPOSED ON UNIT. THIS IS NO LONGER A
 MTS SYSTEM.
 220,701.6
  
 6) NOTE: PLEASE INDICATE THE LOCATION OF
 THE EXISTING MAINS AND DISCONNECTS AND
 GROUPING. 225.34, 225.72
 PLEASE ALSO SEE 230.2E, 701.9
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-08-24 00:00:00IN ELEC FOR REVIEW