Plan Review Notes For Permit 06080391
Permit Number 06080391
Review Stop G
Sequence Number 2
Notes
Date Text
2007-02-14 17:51:04DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEW:
  
 A. PLANS INDICATE NATURAL GAS FUEL, BUT
 MANUF. SHEETS INDICATE DIESEL FUEL.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****CONDITION NOW CHANGED. IS THIS A NATURAL GAS
 GENERATOR, A DIESEL GENERATOR, OR A BI-FUEL GENERATOR??
 PLEASE INDICATE ON PLANS.
  
 B. IF NATURAL GAS FUEL, PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****CONDITION CHANGED. NOW THE GAS IS CONNECTED TO THE
 EXISTING GAS PIPING INSIDE THE BUILDING. THE ISOMETRIC
 SHALL SHOW ALL PIPING FROM THE METER TO THE GENERATOR.
 INDICATE THE TOTAL DEVELOPED LENGTH, TOTAL BTU LOAD ON
 THE SYSTEM, AND INDICATE ALL PIPE SIZES.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTION REQUIRED TO
 INDICATE CLEARANCES REQUIRED FOR
 SERVICING ETC.
 ****THE MAXIMUM BTU LOAD SHALL BE INDICATED ON THE
 MANUF SPECIFICATION SHEETS. THIS IS NOT INDICATED .
  
 3. SUBMIT MANUF. SPECIFICATION SHEETS
 FOR 2PSI TO 1/2PSI REGULATOR. INDICATE
 MODEL NUMBER.
 ****NOT ADDRESSED. NO RESPONSE.
  
 4. 2 PSI TABLE 402.4(3) ONLY GIVES
 INFORMATION UP TO 200'. SEE ATTACHED
 FORMULA, (WEYMOUTH). SUBMIT CALCULATIONS
 SHOWING BTU'S ALLOWED FOR 375' TO
 COMFIRM PIPE SIZE FOR GENERATOR.
 ****NOT ADDRESSED. NO RESPONSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]