| Plan Review Notes For Permit 06080391 |
| Permit Number |
06080391 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-23 17:18:59 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 2.)THE LOCATION OF EQUIPMENT SHALL NOT HINDER, | | | IMPEDE, OR OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF. | | | | | | 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL | | | (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE | | | ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH, | | | AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE | | | LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6). | | | | | | 4.)WHAT IS THE FIRE RATING OF THE ROOF? | | | | | | 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE | | | DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE | | | AIR? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|