2007-02-23 17:18:59*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 2.)THE LOCATION OF EQUIPMENT SHALL NOT HINDER,
 IMPEDE, OR OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF.
  
 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL
 (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE
 ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH,
 AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE
 LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6).
  
 4.)WHAT IS THE FIRE RATING OF THE ROOF?
  
 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE
 DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE
 AIR?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  