Plan Review Notes
Plan Review Notes For Permit 06080391
Permit Number 06080391
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-29 12:07:52***** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE COMMENTS BELOW WHICH ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A *NO* OR *OK* IN FRONT OF
 PREVIOUS NOTE.
  
 **IMPORTANT**
 *PLEASE SEE NEW NOTES NOW ADDED FOR THESE PLANS NOW
 SUBMITTED.
  
  
  
 1) NOTE:NO, PLEASE SEE PERMIT APPLICATION AND SCOPE
 OF WORK STILL DOES NOT CORRELATE.
  
 A) PLEASE SEE SUBMITTALS ARE STILL BEING SUBMITTED
 (ATTACHED TO OLD PLANS) AS DIESEL AND NATURAL GAS?
  
 B) PLEASE SEE TWO DIFFERENT SIZE GENERATOR UNITS ARE
 BEING SHOWN.
  
 C) PLEASE SEE AS STATED PREVIOUSLY ON SITE FUEL IS
 REQUIRED FOR LEGALLY REQUIRED STAND-BY SYSTEMS. MAY NOT
 RELY SOLELY ON THE UTILITIES.
 PLEASE KNOW BASED ON THIS ALONE THIS WILL AFFECT PLANS,
 AND LOCATION OF TANK REQUIRED. PLEASE ALSO KNOW THAT
 BASED ON WHETHER OR NOT THE GENERATOR IS NATURAL GAS OR
 DIESEL, THE FUEL CONSUMPTION SHALL BE STATED FOR
 MINIMUM TIMES.
  
 D) PLEASE KNOW BASED ON *C* ABOVE, THE ON SITE FUEL
 WILL BE REQUIRED TO BE LOCATED AT THE GROUND FLOOR
 LEVEL WHICH WILL REQUIRE SITE PLANS, AND PLANS FOR THIS
 PART OF THE INSTALLATION.
 NFPA-110 CHAPTER 7 WHICH REQUIRES MORE INFORMATION FOR
 THE ENTIRE INSTALLATION. ISOLATION FROM STRUCTURE,
 LOCATION OF FUEL SOURCE ETC.
 PLEASE SEE 701.11(B)(3) FOR ON-SITE FUEL.
 PLEASE SEE 110.3, 90.7, 215.5, 240.4 ETC AS THE REVIEW
 FOR CODE COMPLIANCE CAN NOT BE FULLY ACCOMPLISHED BASED
 ON THE PERMIT APPLICATION SHOWING ONE SYSTEM, AND THE
 PLANS AND THE SPECS SHOWING TWO OTHER SYSTEMS.
  
 E) PLEASE MEANS OF DISCONNECT AND SHUTTING DOWN POWER
 ETC CAN NOT BE VERIFIED. 230.70, 230.72 ETC
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE CORRELATE PLANS, PERMIT APPLICATION AND
 SUBMITTALS.
 PLEASE SEE PLANS INDICATE A DIESEL GEN, AND NATURAL GAS
 GEN.
 PLEASE KNOW A DIESEL GEN WILL NOT BE PERMITTED ON THE
 ROOF TOP. PLEASE ALSO KNOW ANY PERMISSION FOR OTHER GEN
 ON ROOF IS NOT APPROVED AT THIS TIME. PLEASE KNOW A
 CONFERENCE WITH THE FIRE MARSHAL AND PLAN REVIEW FOR
 POSSIBILITIES OF THE PERMITTING A NAT GAS GEN MUST BE
 HELD BEFORE PERMISSION WILL BE GRANTED. SHUT DOWN OF
 FUEL, GEN , MOTOR AND SHUNT OF FEEDERS MAY ALL BE
 REQUIRED ON THE GROUND FLOOR OF BLDG.
 PLEASE KNOW AS MORE THAN ONE SIZE OF GEN AND TYPE FOR
 PRIME MOVER IS BEING SUBMITTED, A COMPLETE REVIEW CAN
 NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-110 PLEASE SEE ALL OF CHAPTER 7. PLEASE
 KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED 7.9.3.1.
 PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES
 REQUIRED. MAY NOT RELY ONLY ON THE UTILITY.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THE VALUE AS SHOWN ON
 APPLICATION BASED ON THE SCOPE OF WORK IS EXTREMELY LOW
 AND A VALUE WILL BE ADJUSTED. THIS NEEDS TO INCLUDE ALL
 STRUCTURAL WORK, GAS/FUEL, TANKS ETC.
 PLEASE SEE 108.3
  
 **PLEASE KNOW, VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOR
 AND MATERIALS. AN INSTALLATION OF GAS
 LINE/ TO ROOF TOP, GEM, ATS ETC.
 FBC 108.3
  
 4) NOTE: OK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]