2006-10-17 14:19:52DENIED:
 1.PLANS INDICATE GAS GENERATOR.THE MANUFACTURE
 SUBMITTAL DATA ALSO INCLUDES SUBMITTAL FOR A NATURAL
 GAS OR LP GENERATOR.PLEASE CORRELATE AND REMOVE
 SUBMITTAL THAT DOES NOT APPLY TO THIS PROJECT.
  
 2.PLEASE COMPLETE THE "STANDARD FEATURES AND
 ACCESSORIES" SHEET IN THE SUBMITTAL PACKAGE THAT WILL
 PERTAIN TO THIS INSTALLATION.
  
 3.PLAN SHEET E2 INDICATES NEW GENERATOR TO BE
 INSTALLED ON "EXISTING EQUIPMENT PLATFORM".PLEASE
 PROVIDE ELEVATION FROM GRADE.
  
 4.PLAN SHEET S3 INDICATES NEW GENERATOR LOCATED ON
 ROOF.PLEASE INDICATE THE FOLLOWING:
 A) HEIGHT OF PARAPET WALL
 B) INDICATE ACCESS TO ROOF
 C) CLEARANCES FROM FRESH AIR INTAKES, WINDOWS,
 DOORS OR COMBUSTIBLE CONSTRUCTION.
  
 5.PLEASE CLARIFY WHAT "EXISTING CABINET" REPRESENTS.
  