Notes
Date Text
2006-09-01 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. PLANS INDICATE NATURAL GAS FUEL, BUT
 MANUF. SHEETS INDICATE DIESEL FUEL.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 B. IF NATURAL GAS FUEL, PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTION REQUIRED TO
 INDICATE CLEARANCES REQUIRED FOR
 SERVICING ETC.
  
 3. SUBMIT MANUF. SPECIFICATION SHEETS
 FOR 2PSI TO 1/2PSI REGULATOR. INDICATE
 MODEL NUMBER.
  
 4. 2 PSI TABLE 402.4(3) ONLY GIVES
 INFORMATION UP TO 200'. SEE ATTACHED
 FORMULA, (WEYMOUTH). SUBMIT CALCULATIONS
 SHOWING BTU'S ALLOWED FOR 375' TO
 COMFIRM PIPE SIZE FOR GENERATOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]