Plan Review Notes
Plan Review Notes For Permit 06080391
Permit Number 06080391
Review Stop FUEL
Sequence Number 1
Notes
Date Text
2006-10-17 13:48:47DENIED:
 PLANS INDICATE NATURAL GAS GENERATOR WHEREAS THE
 MANUFACTURE SUBMITTAL ON THE GENERATOR IS FOR A DIESEL
 GENERATOR.
  
 PLEASE NOTE, SHOULD THE NATURAL GAS GENERATOR BE
 INSTALLED A GAS PERMIT WILL BE REQUIRED INSTEAD OF A
 FUEL PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719.