| Plan Review Notes For Permit 06080391 |
| Permit Number |
06080391 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-13 15:25:51 | *****DENIED***** | | | | | | | | | | | | | | | 1.)NFPA 101, 2003 EDITION SHALL BE REFERENCED. | | | | | | 2.)LOCATION OF STRUCTURE SHALL NOT HINDER, IMPEDE, OR | | | OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF. | | | | | | 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL | | | (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE | | | ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH, | | | AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE | | | LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6). | | | | | | 4.)WHAT IS THE FIRE RATING OF THE ROOF? | | | | | | 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE | | | DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE | | | AIR? | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|