Date Text
2007-02-27 14:26:10 
 REVISION DENIED
  
 1} REGARDING THE FEED TO THE HOUSE FROM THE MAIN PANEL;
 250.32(B)(1) EQUIPMENT GROUNDING CONDUCTOR. AN
 EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN 250.118
 SHALL BE RUN WITH THE SUPPLY CONDUCTORS AND CONNECTED
 TO THE BUILDING OR STRUCTURE DISCONNECTING MEANS AND TO
 THE GROUNDING ELECTRODE(S). THE EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE USED FOR GROUNDING OR BONDING OF
 EQUIPMENT, STRUCTURES, OR FRAMES REQUIRED TO BE
 GROUNDED OR BONDED. THE EQUIPMENT GROUNDING CONDUCTOR
 SHALL BE SIZED IN ACCORDANCE WITH 250.122. ANY
 INSTALLED GROUNDED CONDUCTOR SHALL NOT BE CONNECTED TO
 THE EQUIPMENT GROUNDING CONDUCTOR OR TO THE GROUNDING
 ELECTRODE(S).
  
 2} THE TANKLESS WATER HEATER IS NOT INCLUDED IN THE
 LOAD CALCULATIONS, PLEASE INCLUDE AND RECALCULATE.
  
 3} GIVEN IT CONTAINS OVERCURRENT PROTECTION, PER
 240.22(D), THE TANKLESS HEATER CANNOT BE LOCATED IN A
 CLOSET.
  
 4} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT.THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. LOCATE ON THE PLAN.
  
 5} 210.52(E)-) OUTDOOR OUTLETS. FOR A ONE-FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (61/2
 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND
 BACK OF THE DWELLING. SEE 210.8(A)(3). LOCATE ON THE
 PLAN.
  
 6} THE DISCONNECTING MEANS FOR THE CONDENSER IS IN
 VIOLATION OF 110.26 CLEARANCE REQUIREMENTS.
  
 7} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. PLEASE LOCATE ON THE
 PLAN.
  
 8} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.FOR THE NEW 200 AMP PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER