| 2007-02-26 15:11:25 | |
| | |
| | REVISION DENIED |
| | |
| | 1} REGARDING THE FEED TO THE HOUSE FROM THE MAIN PANEL; |
| | 250.32(B)(1) EQUIPMENT GROUNDING CONDUCTOR. AN |
| | EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN 250.118 |
| | SHALL BE RUN WITH THE SUPPLY CONDUCTORS AND CONNECTED |
| | TO THE BUILDING OR STRUCTURE DISCONNECTING MEANS AND TO |
| | THE GROUNDING ELECTRODE(S). THE EQUIPMENT GROUNDING |
| | CONDUCTOR SHALL BE USED FOR GROUNDING OR BONDING OF |
| | EQUIPMENT, STRUCTURES, OR FRAMES REQUIRED TO BE |
| | GROUNDED OR BONDED. THE EQUIPMENT GROUNDING CONDUCTOR |
| | SHALL BE SIZED IN ACCORDANCE WITH 250.122. ANY |
| | INSTALLED GROUNDED CONDUCTOR SHALL NOT BE CONNECTED TO |
| | THE EQUIPMENT GROUNDING CONDUCTOR OR TO THE GROUNDING |
| | ELECTRODE(S). |
| | |
| | 2} THE TANKLESS WATER HEATER IS NOT INCLUDED IN THE |
| | LOAD CALCULATIONS, PLEASE INCLUDE AND RECALCULATE. |
| | |
| | 3} GIVEN IT CONTAINS OVERCURRENT PROTECTION, PER |
| | 240.22(D), THE TANKLESS HEATER CANNOT BE LOCATED IN A |
| | CLOSET. |
| | |
| | 4} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT.THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. LOCATE ON THE PLAN. |
| | |
| | 5} 210.52(E)-) OUTDOOR OUTLETS. FOR A ONE-FAMILY |
| | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS |
| | AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (61/2 |
| | FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND |
| | BACK OF THE DWELLING. SEE 210.8(A)(3). LOCATE ON THE |
| | PLAN. |
| | |
| | 6} THE DISCONNECTING MEANS FOR THE CONDENSER IS IN |
| | VIOLATION OF 110.26 CLEARANCE REQUIREMENTS. |
| | |
| | 7} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. PLEASE LOCATE ON THE |
| | PLAN. |
| | |
| | 8} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND |
| | 106.3.5.4(8) FBC.FOR THE NEW 200 AMP PANEL. |
| | |
| | 9} THE DESIGNER OF RECORD MUST SIGN DATE AND SEAL THE |
| | PLANS 471-481 FS OR MUST PRINT AND SIGN PER 106.3.4.2. |
| | FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |