Plan Review Notes
Plan Review Notes For Permit 06080370
Permit Number 06080370
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-15 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20
 AMP RECEPTACLE PER 210.11(C) (3),
 LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 2} 210.8(A)(7)GFI REQUIRED@WET BAR SINKS
 ? WHERE THE RECEPTACLES ARE INSTALLED TO
 SERVE THE COUNTERTOP SURFACES AND ARE
 LOCATED WITHIN 1.8 M (6 FT) OF THE
 OUTSIDE EDGE OF THE WET BAR SINK.RE:
 CABANA.
  
 3} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 4} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3). THE
 CABANA MUST ALSO COMPLY.
  
 5} A #6 EQUIPMENT GROUND IS REQUIRED TO
 BE RAN WITH THE SUB FEEDER PER 250.110.
  
 IF THERE AR ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  