Plan Review Notes
Plan Review Notes For Permit 06080369
Permit Number 06080369
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-04 00:00:001) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _XX__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE 2/_3__ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _XX__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 2) FBC 1609THE SYSTEM SELECTED FROM
 THE SUBMITTED FLAT ROOF PRODUCT APPROVAL
 NOA HAS A MAXIMUM DESIGN PRESSURE OF
 LESS THAN -89 PSF AND CITES GENERAL
 LIMITATION #9 (SEE PAGE 39_ OF _45_).
 GENERAL LIMITATION #9 PROHIBITS RATIONAL
 ANALYSIS OR EXTRAPOLATION TO ENHANCE THE
 UPLIFT PRESSURE AT PERIMETER AND CORNER
 AREAS BY REDUCING THE FASTENER SPACING
 IN THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  