| Notes |
| Date |
Text |
| 2006-12-20 10:45:37 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1}PROVIDE LOAD CALCULATIONS PER ARTICLE 220. SIZE THE | | | SERVICE CONDUCTORS ACCORDINGLY, SEE 310.16. | | | | | | 2}PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 3}THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH | | | 250.66. SEE NOTE #1 REGARDING THE SUM OF THE SERVICE | | | ENTRANCE CONDUCTORS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|