 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}PROVIDE LOAD CALCULATIONS PER ARTICLE 220. SIZE THE
 SERVICE CONDUCTORS ACCORDINGLY, SEE 310.16.
  
 2}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3}THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH
 250.66. SEE NOTE #1 REGARDING THE SUM OF THE SERVICE
 ENTRANCE CONDUCTORS.
  