Plan Review Notes
Plan Review Notes For Permit 06080340
Permit Number 06080340
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-16 00:00:00 
 DENIED
  
 1) A CERTIFICATE OF AUTHORIZATION SHALL
 BE REQUIRED FOR A CORPORATION, LIMITED
 LIABILITY COMPANY, OR PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 PER 481.219(2) F.S.
  
 2) PROVIDE OCCUPANCY AND CONSTRUCTION
 TYPE PER 106.3.5 FBC*
  
 3) PROVIDE WIND DESIGN DATA ON DRAWINGS
 PER 1603.1.4 FBC PLEASE INCLUDE THE
 COMPONENT AND CLADDING PRESSURES FOR THE
 OPENINGS
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ****NOTE PRODUCT APPROVALS ARE REQUIRED
 FOR DOORS, WINDOWS, BAHAMA SHUTTERS AND
 ROOF COVERING****
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) WINDOWS AND DOORS UP TO 30 FT ABOVE
 GRADE REQUIRED TO BE LARGE MISSILE
 IMPACT RESISTANT OR REQUIRE SHUTTERS
 (PLEASE SEE CITY THAT IS ENCLOSED AS
 THEIR ARE MORE REQUIREMENTS IF SHUTTERS
 ARE USED)
  
 7) PROVIDE SIZES FOR WINDOWS AND DOORS
 TO BE REPLACED TO CONFIRM DESIGN
 PRESSURES WITH PRODUCT APPROVAL
 PRESSURES
  
 8) PROVIDE INFORMATION ON THE ATTACHMENT
 METHOD FOR THE NEW BUCKS
  
 9) SIGNS AND FENCE REQUIRE SEPERATE
 PERMITS
  
 10) SUBMIT ENGINEERED TRUSS DRAWINGS
 THAT COMPLY WITH R802.10.1 FBC WITH
 PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 11) PROVIDE MINIMUM NAIL/FASTENER
 PATTERN FOR ROOF SHEATHING PER 2304.9.1
 FBC
  
 12) PROVIDE MORE DETAIL ON PARAPET, IS
 LOWER SECTION EXISTING OR ADDED TO THE
 EXISTING WALLS?
  
 13) PROVIDE INSULATION VALUE TO BE ADDED
 TO THE NEW CEILING
  
 14) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  