| Date |
Text |
| 2006-08-16 00:00:00 | |
| | DENIED |
| | |
| | 1) A CERTIFICATE OF AUTHORIZATION SHALL |
| | BE REQUIRED FOR A CORPORATION, LIMITED |
| | LIABILITY COMPANY, OR PARTNERSHIP, |
| | OFFERING ARCHITECTURAL SERVICES TO THE |
| | PUBLIC JOINTLY OR SEPARATELY. |
| | PER 481.219(2) F.S. |
| | |
| | 2) PROVIDE OCCUPANCY AND CONSTRUCTION |
| | TYPE PER 106.3.5 FBC* |
| | |
| | 3) PROVIDE WIND DESIGN DATA ON DRAWINGS |
| | PER 1603.1.4 FBC PLEASE INCLUDE THE |
| | COMPONENT AND CLADDING PRESSURES FOR THE |
| | OPENINGS |
| | |
| | 4) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | ****NOTE PRODUCT APPROVALS ARE REQUIRED |
| | FOR DOORS, WINDOWS, BAHAMA SHUTTERS AND |
| | ROOF COVERING**** |
| | |
| | 5) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 6) WINDOWS AND DOORS UP TO 30 FT ABOVE |
| | GRADE REQUIRED TO BE LARGE MISSILE |
| | IMPACT RESISTANT OR REQUIRE SHUTTERS |
| | (PLEASE SEE CITY THAT IS ENCLOSED AS |
| | THEIR ARE MORE REQUIREMENTS IF SHUTTERS |
| | ARE USED) |
| | |
| | 7) PROVIDE SIZES FOR WINDOWS AND DOORS |
| | TO BE REPLACED TO CONFIRM DESIGN |
| | PRESSURES WITH PRODUCT APPROVAL |
| | PRESSURES |
| | |
| | 8) PROVIDE INFORMATION ON THE ATTACHMENT |
| | METHOD FOR THE NEW BUCKS |
| | |
| | 9) SIGNS AND FENCE REQUIRE SEPERATE |
| | PERMITS |
| | |
| | 10) SUBMIT ENGINEERED TRUSS DRAWINGS |
| | THAT COMPLY WITH R802.10.1 FBC WITH |
| | PERMIT APPLICATION OR BEFORE |
| | INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 11) PROVIDE MINIMUM NAIL/FASTENER |
| | PATTERN FOR ROOF SHEATHING PER 2304.9.1 |
| | FBC |
| | |
| | 12) PROVIDE MORE DETAIL ON PARAPET, IS |
| | LOWER SECTION EXISTING OR ADDED TO THE |
| | EXISTING WALLS? |
| | |
| | 13) PROVIDE INSULATION VALUE TO BE ADDED |
| | TO THE NEW CEILING |
| | |
| | 14) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | |
| | BLDG PLAN REVIEW |