| Plan Review Notes For Permit 06080332 |
| Permit Number |
06080332 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-23 17:41:51 | | | | | | | DENIED | | | | | | PRODUCT APPROVALS ARE INCOMPLETE | | | | | | 1)THERMA-TRU "BENCHMARK" SERIES DOOR NOA HAS EXPIRED | | | ALSO IT IS FOR DOORS WITH SIDELITES OF WHICH THEIR ARE | | | NONE PRESENT ON THE DRAWINGS. PROVIDE PRODUCT APPROVAL | | | FOR THE HOLLOW METAL ENTRY DOOR. | | | | | | 2)PROVIDE PRODUCT APPROVAL FOR THE FRENCH DOORS SHOWN | | | ON THE ELEVATION DRAWINGS (STATED AS PGT) THE FLORIDA | | | APPROVAL SUBMITTED FOR THERMA-TRU (FL# 5262) IS NOT FOR | | | THE ABOVE DOOR AND CANNOT BE USED FOR GLAZED DOORS SUCH | | | AS THE FRENCH DOORS. | | | | | | 3)PROVIDE PRODUCT APPROVALS FOR THE CASTCRETE | | | LINTELS. | | | | | | 4)PROVIDE PRODUCT APPROVALS FOR THE HURRICANE | | | STRAPS/ANCHORS/TIES OR PROVIDE AN INDEX WITH ALL STRAPS | | | TO BE USED AND THERE FL#'S | | | | | | 5)PROVIDE THE FLORIDA STATEWIDE PRODUCT APPROVAL FOR | | | THE HANSON ROOF TILE ( FL# 3506) | | | | | | 6)THE FEES FOR THE INCREASED VALUE AND RADON WHERE | | | NOT PAID IN THE AMOUNT OF $581.75 ,THIS IS REQUIRED TO | | | BE PAID IN FULL BEFORE FURTHER PLAN REVIEW IS | | | PERFORMED. | | | | | | 7)THIS WAS THE 2ND RESUB AND IS NOT FREE CHARGES FOR | | | THIS AND FUTURE RESUBS WILL BE CHARGED. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|