| 2007-04-19 19:07:23 | |
| | |
| | DENIED |
| | |
| | THE FOLLOWING PLAN REVIEW NOTES WERE NOT ADDRESSED: |
| | |
| | 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, |
| | AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL (561) |
| | 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 5)THE MIN SOIL BEARING CAPACITY THAT IS REQUIRED BY |
| | THE DESIGNER (2500 PSF) AND THE SOIL BEARING CAPACITY |
| | IN THE SOIL REPORT (2000 PSF) DO NOT MATCH *****PER |
| | 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH |
| | THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| | SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" *** |
| | |
| | 7 & 9) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES |
| | OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA |
| | STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT |
| | LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE |
| | PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND |
| | THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON |
| | WWW.FLORIDABUILDING.ORG |
| | ********THE CITY OF WEST PALM BEACH REQUIRES THE |
| | FLORIDA STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED******* PLEASE SEE |
| | EXAMPLE FOR YOUR PGT HORIZONTAL SLIDERS ENCLOSED. |
| | FLORIDA PRODUCT APPROVAL NUMBERS ARE MARKED ON THE |
| | NOA'S SOME OF THE NOA'S ARE OUTDATED ALSO |
| | |
| | 11)THE FOLLOWING PRODUCT APPROVALS ARE MISSING FROM |
| | THE PACKAGE |
| | ***** STILL REQUIRE PRE CAST LINTELS AND HURRICANE |
| | ANCHORS/TIESAND ALSO REQUIRED FOR PGT FRENCH |
| | DOORS***** |
| | |
| | 12)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | ****THE TRUSS DRAWINGS MUST BE SUBMITTED PRIOR TO |
| | SETTING OF TRUSSES***** |
| | |
| | 15)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | *****PLEASE NOTE THAT ALL ROOF AREAS MUST BE ACCESSED |
| | LEAVE OPENING IN PLYWOOD WHERE ROOF TRUSSES |
| | INTERSECT***** |
| | |
| | 16)PROVIDE MIN ROOF SHEATHING ATTACHMENT |
| | PER TABLE 2304.9.1 FBC |
| | *****SECTION R803.2.3.1 FBC RES. BETTER STATES THE |
| | PATTERN THAT IS REQUIRED ( 8D RING SHANK NAILS SPACED |
| | AT 6" EDGE & 6" IN THE FIELD EXCEPT ZONE 3 IN WIND |
| | ZONES OF 130 MPH OR GREATER WHERE 4" EDGES & 6" FIELD |
| | IS REQUIRED)****** |
| | |
| | 17)PROVIDE ENGINEERED SUBSTRATE ATTACHMENT FOR WOOD |
| | BUCKS PER 1714.5.4.1 FBC |
| | *****PLEASE NOTE THAT NOA'S SHOW "APPROVED BUCKS" WHICH |
| | MEANS DESIGNED BY OTHERS, WE TYPICALLY SEE 1X4 AND 2X4 |
| | APPLICATIONS IN THE FIELD THEREFORE REQUIRE BOTH |
| | DETAILS WITH ATTACHMENT METHODS SHOWN ON THE DRAWINGS |
| | |
| | NEW COMMENTS |
| | |
| | 1)PROVIDE LINTEL LENGTHS THAT WILL BE USED FOR EACH |
| | OPENING FOR COMPLIANCE WITH2104.1.5 FBC MIN 4" |
| | BEARING |
| | |
| | 2)SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. PLEASE SUBMIT ON CORRECT FORM, SEE |
| | MECHANICAL REVIEW |
| | |
| | 3)BEFORE FURTHER REVIEW ALL FEES MUST BE PAID IN |
| | FULL |
| | |
| | NOTE: |
| | FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH ADMINISTATIVE AMMENDMENTS TO |
| | FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | FBC RES. = FLORIDA BUILDING CODE RESIDENTIAL 2004 |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |