Plan Review Notes
Plan Review Notes For Permit 06080332
Permit Number 06080332
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-14 00:00:00 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 4) INDEX SHEET REQUIES UPDATED
 INFORMATION ON THE FRONT AND SIDE
 SETBACKS THAT ARE PROVIDED
  
 5) THE MIN SOIL BEARING CAPACITY THAT IS
 REQUIRED BY THE DESIGNER (2500 PSF) AND
 THE SOIL BEARING CAPACITY IN THE SOIL
 REPORT (2000) DO NOT MATCH
  
 6) PLEASE SUBMIT 2 COPIES OF ALL
 CONSTRUTION DOCUMENTS THIS INCLUDES SOIL
 REPORTS, SURVEYS, ENERGY CALC'S, PRODUCT
 APPROVALS, ETC.
  
 7) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 8) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9) PRODUCT APPROVALS THAT WERE SUBMITTED
 SHALL BE SUBMITTED WITH THE STATE COVER
 SHEETS WHERE APPLICABLE
  
 10) PRODUCT APPROVALS WERE SUBMITTED FOR
 HORIZONTAL SLIDING WINDOWS AND NONE ARE
 PRESNT ON THE DRAWINGS
  
 11) THE FOLLOWING PRODUCT APPROVALS ARE
 MISSING FROM THE PACKAGE (SH WINDOWS,
 MULLIONS FOR WINDOWS THAT ARE JIONED
 TOGETHER, FRENCH DOORS,SLIDING GLASS
 DOORS,WOOD ANCHORS AND TIES
  
 12) SUBMIT ENGINEERED TRUSS DRAWINGS
 THAT COMPLY WITH R802.10.1 FBC WITH
 PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 13) PROVIDE AT MINIMUM 1 ACCESSIBLE
 BATHROOM PER R322.1.1 FBC
  
 14) THE SH24 WINDOWS SPECIFIED ON THE
 DRAWINGS DO NOT MEET THE REQUIREMENTS
 FOR EMERGENCY EGRESS AS STIPULATED PER
 R310.1 - R310.1.4 FBC
  
 15) PROVIDE ATTIC ACCESS ON DRAWINGS PER
 R807.1
  
 16) PROVIDE MIN ROOF SHEATHING
 ATTACHMENT PER TABLE 2304.9.1 FBC
  
 17) PROVIDE BUCK ATTACHMENT DETAIL FOR
 2X BUCKS AS MANY INSTALLATIONS USE 2X
 INSTEAD OF 1X, ALSO NOTE THAT BUCK FOR
 GARAGE DOOR AS PER NOA
  
 18) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  