| 2006-12-15 12:55:52 | BUILDING PLAN REVIEW |
| | PERMIT:06080308 |
| | ADD:63641STST. |
| | CONT: BILL MARTIN RENOVATIONS, INC. |
| | TEL: (561)863-8227 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | |
| | 1) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. NOTE: THE OFFICE IS IN A NEWS LOCATION SEE |
| | NEW ADDRESS IN PACKAGE. THIS IS REQUIRED BECAUSE THE |
| | PORCH IS NOW LIVING SPACE. |
| | |
| | 3) 2004 F.B.C. 1203.4.2.1 BATHROOMS |
| | ROOMS CONTAINING BATHTUBS,SHOWERS,SPAS AND SIMILAR |
| | BATHING FIXTURES SHALL BE MECHANICALLY VENTILATED IN |
| | ACCORDANCE WITH THE F.B.C. MECHANICAL. THIS INFORMATION |
| | IS NOT SHOWN FOR THE NEW BATHROOM. |
| | |
| | 4) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC*. |
| | |
| | 5)ON SHEET 1 OF 4, WHY IS THE LAYOUT DIFFERENT IF |
| | THAT AREA IS EXISTING? IF THERE IS NO ALTERATION TO THE |
| | STRUCTURE, SHOW MATCHING FLOOR PLAN ON ALL PAGES. |
| | INDICATE ON THE DRAWINGS WHERE ALL THE CHANGES ARE. |
| | |
| | 6) 1609.1.4 PROTECTION OF OPENINGS. |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. THE NEW WINDOWS |
| | ARE NOT IMPACT RESISTANT THEREFORE, THEY NEED HURRICANE |
| | PROTECTION. SUBMIT PRODUCT APPROVAL FOR THE HURRICANE |
| | SHUTTERS. |
| | |
| | NOTE: ADDITIONAL PERMITS WILL BE REQUIRED FOR |
| | ELECTRICAL AND MECHNICAL WORK. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |