| 2006-09-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- BRING DRAWINGS TO PALM BEACH COUNTY |
| | FOR IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND COPY OF PAID RECEIPT. |
| | |
| | 3- A) SURVEY NOTE #8 STATES THAT THIS |
| | SURVEY CAN NOT BE USED FOR CONSTRUCTION |
| | PURPOSES. PROVIDE REVISED SURVEY. |
| | B) FLOOD ZONE IS "C" NOT X N/A. REVISE |
| | SURVEY AS REQUIRED. |
| | |
| | 4- NEED SMOKE DETECTORS AS REQUIRED BY |
| | SECTIONS R311.1 AND R313.1.1 OF 2004 |
| | RESIDENTIAL CODE. |
| | |
| | 5- NEED ENERGY CALCULATIONS AS REQUIRED |
| | BY CHAPTER 13 FBC 2004. |
| | |
| | 6- PLANS ARE NOT CLEAR. NEED LEGEND TO |
| | IDENTIFY WHICH WALLS ARE NEW, WHICH ARE |
| | EXISTING AND WHICH ONES ARE GOING TO BE |
| | REMOVED. SECTION 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 7- NEED TO SPECIFY SIZE OF WINDOWS AND |
| | DOORS. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 8- ENGINEER TO SPECIFY ALL DESIGN |
| | CRITERIA AS REQUIRED BY SECTION R301 |
| | 2004 RESIDENTIAL CODE. |
| | |
| | 9- SPECIFY ROOF SHEATHING THICKNESS AND |
| | FASTENING. SEE TABLE 2304.9.1 FBC 2004. |
| | |
| | 10- A) PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS. NEED KEY PLAN AN A |
| | COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED INSTALLATION SCHEDULE SAMPLE |
| | FROM THE CITY IMPLEMENTATION STANDARD |
| | FOR WIND-BORNE DEBRIS IMPACT PROTECTION. |
| | B) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR STORM SHUTTERS. |
| | |
| | 11- ENGINEER TO IDENTIFY SPECIFIC LEVEL |
| | OF ALTERATION THAT APPLIES TO THIS HOUSE |
| | AS REQ'D BY SEC. 301.5 0F 2004 FLORIDA |
| | EXISTING BUILDING CODE. |
| | |
| | 12- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) FLAT ROOF SYSTEM. |
| | ***NOTE: NEED TO IDENTIFY SPECIFIC FLAT |
| | ROOF APPROVED ASSEMBLY AND COMPLY WITH |
| | GENERAL LIMITATION #7 OR #9 AS REQUIRED. |
| | SEE ATTACHED COPY OF CITY POLICY FOR |
| | ROOFING PERMITS. |
| | B) ALL STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS.SEE PLANS AND DETAILS. |
| | |
| | 13- ENGINEER TO REVIEW AND APPROVE IN |
| | WRITTING ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMNTS |
| | TO FBC 2004. |
| | |
| | 14- BUILDING PERMIT VALUATION DECLARED |
| | ON THE PERMIT APPLICATION IS |
| | UNDERESTIMATED. PROVIDE CORRECT |
| | VALUATION OR IT WILL BE ESTIMATED AS |
| | DESCRIBED IN SEC. 108.3 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 15- ONLY TWO SETS OF DRAWINGS AND |
| | PRODUCT APPROVALS ARE REQUIRED. |
| | |
| | 16- TYPICAL WALL SECTION: |
| | A) R-30 INSULATION DOESN'T FIT IN 2X6 |
| | RAFTERS. REVISE AS REQUIRED. |
| | B) R-19 INSULATIONDOESN'T FIT IN 2X4 |
| | STUDS. REVISE AS REQUIRED. |
| | C) WOOD NEED TO BE MIN. 6" ABOVE GRADE |
| | AS REQUIRED BY SEC. R319.1(5). REVISE |
| | WALL SECTION AS REQUIRED. |
| | D) SPECIFY SIZE OF BOLT SPECIFIED TO |
| | ATTACH LEDGER TO EXISTING WALL. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | E) SPECIFY ROOF VENTILATION AS REQUIRED |
| | BY SEC. R806 2004 RESIDENTIAL CODE. |
| | F) CLARIFY NOTE REGARDING TRUSS |
| | ATTACHED WITH MTS12. THERE ARE NOT |
| | TRUSSES IN THIS ROOF. REVISE AS |
| | REQUIRED. |
| | G) PROVIDE DETAIL SHOWING HOW IS THE |
| | SIMPSON MSTA12 ATTACHED TO 2X4 STUD AT |
| | BOTTOM?. SEC. 106.1.2 CITY AMENDMENTS. |
| | |
| | 17- WIND LOAD DRAWINGS ON SHEET #3 ARE |
| | FOR SLIDING GLASS DOORS AND GARAGE |
| | DOORS. THERE ARE NOT THESE TYPES OF |
| | DOORS IN THIS PROJECT AND DRAWINGS ARE |
| | NOT LEGIBLE. |
| | |
| | 18- REVISE DOOR AND WINDOW JAMB DETAILS. |
| | TYPICAL WALL SECTIONS SPECIFIES 2X4 |
| | FRAMING, WHILE DETAILS CALL FOR 2X6. |
| | REVISE AS REQUIRED. |
| | |
| | 19- CONTRACTOR TO UPDATE THE LICENSE |
| | RECORDS WITH THE PERMIT CLERK. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |