| 2006-08-16 00:00:00 | * UNSAT * |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS |
| | REFLECT THE FOLLWOIGN CODES AT A MIN. |
| | NFPA-70 2002, NFPA-30A 2003. |
| | |
| | 2) NOTE: PLEASE PROVIDE A LAYOUT SHWOIGN |
| | THE CLASS LOCATIONS AS SPECIFIED IN NEC |
| | ART 514. |
| | |
| | 3) NOTE: PLEASE SHOW ALL ELECTRICAL |
| | EQUIPMENT ON ELECTRICAL SITE PLAN AS |
| | SHOWN ON RISER DIAGRAM. |
| | FBC 106.1.2, NEC 514 |
| | |
| | 4) NOTE: PLEASE PROVIDE MANUFACTURES |
| | SPECS/CUT SHEETS ON EQUIPMENT /FUEL |
| | PUMPS, TANKS ETC. PLEASE SEE COMMENTS |
| | FROM OTHER TRADES WHICH MAY ALSO REQUIRE |
| | TO REVIEW SUCH ITEMS. |
| | PLEASE BE SURE ALL ARE LISTED BY A NRTL. |
| | 110.3,90.7 |
| | FBC 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |