Plan Review Notes
Plan Review Notes For Permit 06080146
Permit Number 06080146
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-15 00:00:00 
  
 DENIED
  
 1) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENCE NUMBER
 ON EACH SHEET THAT BEARS THEIR SEAL PER
 61G15-23.002(2) FAC
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) PROVIDE WIND DESIGN DATA ON DRAWINGS
 PER 1603.1.4 FBC
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING
 (ROOF COVERING REQUIRES PRODUCT
 APPROVAL)
  
 5) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 6) PROVIDE MIN ROOF SHEATHING ATTACHMENT
 PER TABLE 2304.9.1 FBC
  
 7) THE SEAL USED BY THE ENGINEER IS NO
 LONGER VALID AND DOES NOT COMPLY WITH
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS MANDATE THAT THIS TYPE OF SEAL
 NOT BE USED AFTER DEC. 31, 2005
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716