| Date |
Text |
| 2006-10-12 10:42:44 | ** UNSAT 2ND REVIEW*** |
| | |
| | PLEASE SEE SOME NTOES FROM PREVIOUS REVIEW WHICH ARE |
| | STILL IN NEED OF ADDRESSING. |
| | PLEASE SEE SONE NEW COMMENTS BASED ON PLANS BEING |
| | SUBMITTED. |
| | |
| | 1) NOTE: NO, COULD NOT LOCATE THIS? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE DECLARE USE. PLEASE SEE |
| | TYPE OF MERCHANTILE AND WAREHOUSE USE |
| | MUST BE STATED. PLEASE SEE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | PLEASE SEE CHAPTER 5 IN THE NEC FOR ANY |
| | HAZARDOUS LOCATIONS/STORAGE ETC. |
| | |
| | 2) NOTE: NO, PLEASE SEE ALL CIRCUITING IS SHOWN, |
| | HOWEVER PLEASE SEE SPECIFIC AREAS AND ROOMS ARE NOT |
| | SHOWING DESIGNATIONS ON PLANS AND ON PANEL SCHEDULES.; |
| | PLEASE SEE SCHEDULE MENTYIONS "LTS" OR RECEPT" W/OUT |
| | ANY LOCATION. |
| | PLEASE ALSO SEE ELECTRICAL "POWER PLAN" IS BEING SHOWN |
| | ON THE ARCHITECTURAL SHEETS AND NOT ON THE "E" SHEETS? |
| | PLEASE KNOW, IF BUIDLIGN REVIEW IS OK, THESE SHEETS MAY |
| | NOT BE STAMPED AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULES. |
| | PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC |
| | TO AREAS, ROOMS ETC. |
| | 408.4,240.4,310.16 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: OK/NO, PLEASE SEE THE RECEPTSARE SHOWN, |
| | HOWEVER PLEASE CLARIFY/ HOW THE LOAD IS DERIVED AND |
| | SHOWN IN LOAD CALCULATIONS FOR THE SHOW WINDOWS PER |
| | 220.12. THIS COULD NOT BE LCOATED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING SHOW WINDOW |
| | RECEPTS REQUIRED. |
| | 210.62, 220.12 |
| | |
| | 4) NOTE:NO, PLEASE SEE A RECEPT IS SHOWN , HOWEVER |
| | NOT PER 600.5 WHICH REQUIRES A MINDEDICATED CIRCUIT |
| | AND ALSO THERE SHOULD BE A MIN VA FIGURED FOR THIS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING SIGN |
| | CIRCUIT.600.5 |
| | |
| | 5) NOTE:NO, PLEASE SEE SOME ITEMS ARE SHOWN, BUT NOT |
| | ALL. PLEASE SEE "SEPARATE SPACES" AND TYPES OF |
| | DEVICES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13 FOR |
| | LIGHTING CONTROLS REQUIRED. THIS SPACE |
| | IS LOCATED IN A BLDG GREATER THAN 5000 |
| | SQ FT. |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3 |
| | |
| | 6) NOTE: NO, PLEASE SEE PLANS STILL INDICATE "LATEST |
| | EDITION" |
| | PLEASE SEEE "E" SHEETS". |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS MENTIONS THE |
| | "LATEST EDITIONS" OD THE CODES, HOWEVER |
| | PLEASE KNOW THAT THE LATEST EDITIONS OF |
| | THE CODE WHICH IS OUT AND AVAILABLE IS |
| | NOT YET ADOPTED BY THE STATE. |
| | PLEASE SEE THE FOLLOWING CODES AT A MIN |
| | SHALL BE REFLECTED ON THE ELECTRICAL |
| | PLANS. |
| | 2002 NFPA-70 , 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | 7) NOTE: NO, PLEASE SEE ONLY THE FIRM LICENSE NUMBER IS |
| | SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE THE PRINTED |
| | LICENSE # OF THE ARCHITECT IS ON SAID |
| | TITLE BLOCK AS REQUIRED PER FAC |
| | 61G1-16.004 |
| | |
| | |
| | ** NEW NOTE ** |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |