Plan Review Notes For Permit 06080143
Permit Number 06080143
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-06 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR THE 2ND FLOOR
 SINK. SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED) NO CABINET DOORS IN
 CLEAR FLOOR SPACE.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS (IF REQUIRED BY SECTION 604.9)
 SECTIONS 606 AND 106.3.5.1.3.
  