| Plan Review Notes For Permit 06080143 |
| Permit Number |
06080143 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-06 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SUBMIT A DETAIL FOR THE 2ND FLOOR | | | SINK. SHOW THE FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD | | | APPROACH REQUIRED) NO CABINET DOORS IN | | | CLEAR FLOOR SPACE. | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | E. 11-4.24.7 FAUCETS | | | | | | 2. SUBMIT A WATER RISER DIAGRAM SHOWING | | | PIPE SIZES, VALVES, AND WATER HAMMER | | | ARRESTORS (IF REQUIRED BY SECTION 604.9) | | | SECTIONS 606 AND 106.3.5.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|