| Date |
Text |
| 2006-08-16 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE DECLARE USE. PLEASE SEE |
| | TYOE OF MERCHANTILE AND WAREHOUSE USE |
| | MUST BE STATED. PLEASE SEE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | PLEASE SEE CHAPTER 5 IN THE NEC FOR ANY |
| | HAZARDOUS LOCATIONS/STORAGE ETC. |
| | |
| | 2) NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULES. |
| | PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC |
| | TO AREAS, ROOMS ETC. |
| | 408.4,240.4,310.16 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE MISSING SHOW WINDOW |
| | RECEPTS REQUIRED. |
| | 210.62, 220.12 |
| | |
| | 4) NOTE: PLEASE SEE MISSING SIGN |
| | CIRCUIT.600.5 |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13 FOR |
| | LIGHTING CONTROLS REQUIRED. THIS SPACE |
| | IS LOCATED IN A BLDG GREATER THAN 5000 |
| | SQ FT. |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3 |
| | |
| | 6) NOTE: PLEASE SEE PLANS MENTIONS THE |
| | "LATEST EDITIONS" OD THE CODES, HOWEVER |
| | PLEASE KNOW THAT THE LATEST EDITIONS OF |
| | THE CODE WHICH IS OUT AND AVAILABLE IS |
| | NOT YET ADOPTED BY THE STATE. |
| | PLEASE SEE THE FOLLOWING CODES AT A MIN |
| | SHALL BE REFLECTED ON THE ELECTRICAL |
| | PLANS. |
| | 2002 NFPA-70 , 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | 7) NOTE: PLEASE BE SURE THE PRINTED |
| | LICENSE # OF THE ARCHITECT IS ON SAID |
| | TITLE BLOCK AS REQUIRED PER FAC |
| | 61G1-16.004 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |