| 2006-08-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:06080143 |
| | ADD: 5405 N. HAVERHILL RD. |
| | CONT: G. W. PURUCKER HOMES INC. |
| | TEL: (561)775-1170 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601, AND LEVEL OF ALTERATION |
| | UNDER 2004 FL EXISTING BLDG |
| | CODE. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 3) ADDITIONAL INFORMATION REQUIRED, |
| | 106.1.2*. PLANS INDICATE THERE IS A |
| | MEZZANINE LEVEL, PROVIDE WHAT WALLS ARE |
| | EXISTING AND WHAT WALLS ARE NEW FIRST |
| | FLOOR AND MEZZANINE LEVEL. |
| | BOTH THE FIRST FLOOR AND MEZZANINE |
| | LEVELS CAN NOT BE TOTALY ENCLOSED. |
| | MEZZANINES BY DEFINTION NEED TO |
| | COMMUNICATE WITH THE ROOM THAT IT IS |
| | LOCATED. EITHER THE FLOORS CAN NOT BE |
| | ENCLOSED ONLY ONE. 505.2. EVEN IF THE |
| | EXCEPTION# 1 OF 505.4 THE AMOUNT OF |
| | OPENNESS REQUIRED THE OCCUPANT LOAD FOR |
| | THE MEZZANINE WOULD BE OVER 10 |
| | OCCUPANTS. THE CONFERENCE ROOM ALONE |
| | 148SQ FT @ 15 SQ FT / PERSON ALONE WOULD |
| | BE AN OCCUPANT LOAD OF 10 PLUS THE |
| | REMAINDER OF THE FLOOR. IF EXCEPTION# 3 |
| | IS TAKEN ONLY 10% OF THE MEZZANINE FLOOR |
| | AREA CAN BE ENCLOSED. |
| | |
| | 4) THESE UNITS ARE CONDOMINIMUM |
| | REQUIRING A UNITY OF TITLE BETWEEN |
| | UNITS. THE PROPOSED BUILDING (UNIT) |
| | STRUCTURE TRANSGRESSES LEGAL BOUNDARY |
| | LINES BETWEEN THE LOTS WHICH COMBINE TO |
| | FORM 'THE SITE'.A 'UNITY OF TITLE' |
| | SHALL BE RECORDED AT THE COUNTY |
| | COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF OF TITLE' DOCUMENT SO |
| | THAT FBC TABLE 600 BOUNDARY LINE |
| | REQUIREMENTS MAY BE DEEMED NOT |
| | APPLICABLE. |
| | |
| | 5) DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY:11-4.1.6(1)(F) |
| | NOTHING IN THIS SECTION SHALL BE |
| | CONSTRUED TO RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY FROM THE |
| | DUTY TO PROVIDE VERTICAL ACCESSIBILITY |
| | TO ALL LEVELS ABOVE AND BELOW OCCUPIABLE |
| | GRADE LEVEL, REGARDLESS OF WHETHER THE |
| | CODE REQUIRES AN ELEVATOR TO BE |
| | INSTALLED IN SUCH BUILDING, STRUCTURE, |
| | OR FACILITY, EXCEPT FOR: (1) ELEVATOR |
| | PITS, ELEVATOR PENTHOUSES, MECHANICAL |
| | ROOMS, PIPING OR EQUIPMENT CATWALKS, AND AUTOMOBILE |
| | LUBRICATION AND MAINTENANCE |
| | PITS AND PLATFORMS; (2) UNOCCUPIABLE |
| | SPACES, SUCH AS ROOMS, ENCLOSED SPACES, |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED |
| | FOR HUMAN OCCUPANCY, FOR PUBLIC |
| | ACCOMMODATIONS, OR FOR WORK AREAS; AND |
| | (3) OCCUPIABLE SPACES AND ROOMS THAT ARE |
| | NOT OPEN TO THE PUBLIC AND THAT HOUSE NO |
| | MORE THAN FIVE PERSONS INCLUDING, BUT |
| | NOT LIMITED TO, EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. HOWEVER, AS |
| | PROVIDED IN SECTION 553.509, FLORIDA |
| | STATUTES , BUILDINGS, STRUCTURES, AND |
| | FACILITIES MUST, AT A MINIMUM, COMPLY |
| | WITH THE REQUIREMENTS OF THE ADAAG. |
| | THEREFORE, FACILITIES SUBJECT TO THE |
| | ADAAG MAY BE REQUIRED TO PROVIDE |
| | VERTICAL ACCESS TO AREAS OTHERWISE |
| | EXEMPT UNDER SECTION 11-4.1.3 (5) OF |
| | THIS CODE. |
| | |
| | 6)TO CLASSIFY THIS SPACE AS A TWO |
| | STORY |
| | UNIT, A EXIT TO THE EXTERIOR WILL BE |
| | REQUIRED. 1017.2.2 ARRANGEMENT. |
| | EXTERIOR EXIT DOORS SHALL LEAD DIRECTLY |
| | TO THE EXIT DISCHARGE OR THE PUBLIC |
| | WAY.1017.1 GENERAL. |
| | |
| | EXITS SHALL COMPLY WITH SECTIONS 1017 |
| | THROUGH 1022 AND THE APPLICABLE |
| | REQUIREMENTS OF SECTIONS 1003 THROUGH |
| | 1012 . AN EXIT SHALL NOT BE USED FOR ANY |
| | PURPOSE THAT INTERFERES WITH ITS |
| | FUNCTION AS A MEANS OF EGRESS. ONCE A |
| | GIVEN LEVEL OF EXIT PROTECTION IS |
| | ACHIEVED, SUCH LEVEL OF PROTECTION SHALL |
| | NOT BE REDUCED UNTIL ARRIVAL AT THE EXIT DISCHARGE. |
| | EXIT |
| | 1017.2 EXTERIOR EXIT DOORS. |
| | BUILDINGS OR STRUCTURES USED FOR HUMAN |
| | OCCUPANCY SHALL HAVE AT LEAST ONE |
| | EXTERIOR DOOR THAT MEETS THE |
| | REQUIREMENTS OF SECTION 1008.1.1 . |
| | |
| | MORE COMMENTS MAY APPEAR AS A RESULT OF |
| | THE RESPONCE COMMENTS. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |