2006-10-22 17:53:16********* UNSAT3RD REVIEW *********
  
  
 ** PLEASE SEE SOME NOTE BELOW ARE THE SAME AS THE TWO
 PREVIOUS REVIEWS.
 PLEASE ALSOSEE NEW NOTES DUE TO CHANGES MADE TO
 PLANS.
  
  
  
 1) NOTE: PLEASE SEE 225.31-225.39. PLEASE SEE MISSING
 REQUIRED MEANS OF DISCONNECT AT DETACHED STRUCTURES.
 PLEASE SEE RISER AND GARAGE PANEL IS BEING SHOWN AS MLO
 WITH NO MAIN?
  
 2) NOTE: PLEASE SEE ARC FAULT PROTECTION IS STILL NOT
 BEING SHOWN FOR ALL "OUTLETS" IN BEDROOM/SLEEPING
 ROOMS. PLEASE SEE 210.12B. PLEASE SEE PANEL SCHEDULES
 STILL ONLY INDICATE FOR WHAT SEEMS TO BEPROTECTION
 FOR RECEPT CIRCUITS. .
  
  
 **NEW NOTES DUE TO CHANGES IN RISER**
  
 3) NOTE: PLEASE CORRELATE RISER WITH PANEL SCHEDULE FOR
 FEEDERS TO GARAGE PANEL.PLEASE SEE RISER SHOWS #3'S
 AND PANEL SCHEDULE SHOWS #6'S?
 PLEASE SEE NEXT COMMENT FOR 240.4,310.16 ETC.
  
 4) NOTE: PLEASE SEE ORIGINAL PLANS CONTAINED LOAD
 CALCULATIONS FOR EACH PANEL, HOWEVER PLEASE SEE PANEL
 "A" AND PANEL "B" DO NOT INDICATE ANY LOADS AND PLEASE
 SEE GARAGE SUB PANEL NOW SHOWS 170A'S OF LOAD. PLEASE
 SEE 220.31 FOR LOAD CALCULATIONS FOR EACH PANEL AND
 SERVICE LOAD CALCS.
 PLEASE INDICATE THE LOAD ON GARAGE PANEL TO VERIFY THE
 FEEDER FROM PANEL "B".
 240.4, 310.16 ETC.
  
 5) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM PANEL "B" TO GARAGE PANEL "C?". 250.32,
 250.110, 250.122
  
 6) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE FOR
 DESIGN PROFESSIONALS WAS GIVEN ON PREVIOUS REVIEW.
 PLEASE SEE FSWHICH STATES THE FEE "SHALL" BE APPLIED.
 AS THERE ARE COMMENTS REPEATED FOR THE SAME CODE
 COMMENTS ON THIS REVIEW, THIS OFFICE IS LEFT TO ASSESS
 A 4X FEE FOR THE PLAN REVIEW. THIS FEE OF $8039.40 MUST
 BE PAID BEFORE PLANS MAY BE RESUBMITTED AS REQUIRED
 UNDER THE FLORIDA STATUE.
 TO DATE CONTACT TO THIS REVIEWER FOR ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO REVIEW HAS NOT BEEN MADE. IT
 IS THE RECOMMENDATION OF THIS REVIEWER TO CALL TO
 ARRANGE A MEETING TO BE HELD TO GO OVER COMMENTS BEFORE
 NEXT RESUB.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved