| 2006-10-22 17:53:16 | ********* UNSAT3RD REVIEW ********* |
| | |
| | |
| | ** PLEASE SEE SOME NOTE BELOW ARE THE SAME AS THE TWO |
| | PREVIOUS REVIEWS. |
| | PLEASE ALSOSEE NEW NOTES DUE TO CHANGES MADE TO |
| | PLANS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE 225.31-225.39. PLEASE SEE MISSING |
| | REQUIRED MEANS OF DISCONNECT AT DETACHED STRUCTURES. |
| | PLEASE SEE RISER AND GARAGE PANEL IS BEING SHOWN AS MLO |
| | WITH NO MAIN? |
| | |
| | 2) NOTE: PLEASE SEE ARC FAULT PROTECTION IS STILL NOT |
| | BEING SHOWN FOR ALL "OUTLETS" IN BEDROOM/SLEEPING |
| | ROOMS. PLEASE SEE 210.12B. PLEASE SEE PANEL SCHEDULES |
| | STILL ONLY INDICATE FOR WHAT SEEMS TO BEPROTECTION |
| | FOR RECEPT CIRCUITS. . |
| | |
| | |
| | **NEW NOTES DUE TO CHANGES IN RISER** |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER WITH PANEL SCHEDULE FOR |
| | FEEDERS TO GARAGE PANEL.PLEASE SEE RISER SHOWS #3'S |
| | AND PANEL SCHEDULE SHOWS #6'S? |
| | PLEASE SEE NEXT COMMENT FOR 240.4,310.16 ETC. |
| | |
| | 4) NOTE: PLEASE SEE ORIGINAL PLANS CONTAINED LOAD |
| | CALCULATIONS FOR EACH PANEL, HOWEVER PLEASE SEE PANEL |
| | "A" AND PANEL "B" DO NOT INDICATE ANY LOADS AND PLEASE |
| | SEE GARAGE SUB PANEL NOW SHOWS 170A'S OF LOAD. PLEASE |
| | SEE 220.31 FOR LOAD CALCULATIONS FOR EACH PANEL AND |
| | SERVICE LOAD CALCS. |
| | PLEASE INDICATE THE LOAD ON GARAGE PANEL TO VERIFY THE |
| | FEEDER FROM PANEL "B". |
| | 240.4, 310.16 ETC. |
| | |
| | 5) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM PANEL "B" TO GARAGE PANEL "C?". 250.32, |
| | 250.110, 250.122 |
| | |
| | 6) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE FOR |
| | DESIGN PROFESSIONALS WAS GIVEN ON PREVIOUS REVIEW. |
| | PLEASE SEE FSWHICH STATES THE FEE "SHALL" BE APPLIED. |
| | AS THERE ARE COMMENTS REPEATED FOR THE SAME CODE |
| | COMMENTS ON THIS REVIEW, THIS OFFICE IS LEFT TO ASSESS |
| | A 4X FEE FOR THE PLAN REVIEW. THIS FEE OF $8039.40 MUST |
| | BE PAID BEFORE PLANS MAY BE RESUBMITTED AS REQUIRED |
| | UNDER THE FLORIDA STATUE. |
| | TO DATE CONTACT TO THIS REVIEWER FOR ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO REVIEW HAS NOT BEEN MADE. IT |
| | IS THE RECOMMENDATION OF THIS REVIEWER TO CALL TO |
| | ARRANGE A MEETING TO BE HELD TO GO OVER COMMENTS BEFORE |
| | NEXT RESUB. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |