| 2006-09-19 00:00:00 | **** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO CHANGES |
| | IN PLANS. |
| | |
| | 1) NOTE:NO, PLEASE SEE RISER AND |
| | PANELS, LOCATIONS ETC ARE NOT CLEAR. |
| | PLEASE SEE PLANS INDICATE THE SERVICE |
| | NOW BEING LOCATED AT THE MAIN HOUSE, |
| | ALTHOUGH, PLEASE SEE PANEL SCHEDULES |
| | STILL SAY "GARAGE"?? |
| | PLEASE SEE 225.31-225.39 FOR PANELS, |
| | CIRCUITS, DISCONNECTING MEANS ETC. IF |
| | SERVICE IS GOING TO BE AT THE MAIN |
| | HOUSE, THEN THE BRANCH CIRCUITS AS SHOWN |
| | ON PANEL SCHEDULES MAY NOT COME FROM |
| | MAIN HOUSE. WITH THE # OF CIRCUITS |
| | SHOWN, IT MUST MEET CODES ABOVE. |
| | |
| | 2) NOTE: PLEASE SEE ONCE THE ELECTRICAL |
| | SERVICE IS FIGURED OUT AND WHERE THE |
| | PANELS ARE, AND NEW PANEL AT THE |
| | DETACHED STRUCTURE ETC, THEN PLEASE SEE |
| | 250.32 FOR GROUNDING ELECTRODE SYSTEM TO |
| | BE SHOWN. |
| | 250.66, 250.122 |
| | |
| | 3) NOTE: PLEASE SEE NOW A/C AHU LOADS |
| | AND OCP ARE NOW SHOWN, HOWEVER PLEASE |
| | SEE 424.3B FOR MIN OCP FOR AHU#2. |
| | PLEASE ADJUST. |
| | MIN 125%. |
| | |
| | 4) NOTE: PLEASE SEE THAT PLANS ARE |
| | REQUIRED TO STATE THE 2002 NFPA-72. |
| | 11.5.1.1,11.8.3 |
| | |
| | 5) NOTE: PLEASE SEE 2002 210.12 AS ALL |
| | CIRCUITS IN BEDRMS AND AREAS OF THE LIKE |
| | AS ADAPTBALE SLEEPING RMS ARE REQUIRED |
| | TO HAVE ARC FAULT PROTECTION FOR ALL |
| | CIRCUITS INTO THESE AREAS. PLEASE SEE |
| | SOME ARE SHOWN W/ AND SOME ARE SHOWN |
| | W/OUT. |
| | |
| | 6) NOTE: PLEASE SEE SEE BREAKFAST AREAS, |
| | DINING AREAS AND AREAS OF THE LIKE SHALL |
| | BE ON ONE OR MORE OF THE REQUIRED SMALL |
| | APPLICANCE CIRCUUITS. PLEASE KNOW, EACH |
| | OF THESE CIRCUITS ABOVE THE TWO MINIMUM |
| | IS REQUIRED TO BE 20A AND OT BE FIGURED |
| | AT A MIN OF 1500VA EACH. |
| | 210.52B1,210.11C1,220.16 |
| | |
| | 7) NOTE: PLEASE SEE RISER, IF UNDER |
| | GROUND SEC'S FROM METER CAN TO FPL ARE |
| | GOING TO BE INSTALLED PER FPL, PLEASE DO |
| | NOT INCLUDE ON RISER. (NOTE "BY FPL") , |
| | IF THESE ARE GOING TO BE INSTALED BY THE |
| | ELECTRICAL CONTRACTOR TO AN FPL |
| | HAND-HOLE THEN PLEASE SEE MIN SIZE AS |
| | DEFINED IN 310.15B6. SINGLE SET, 3-WIRE |
| | ONLY. 400MCM COPPER OR 600MCM ALUM MIN. |
| | 310.15B6. |
| | ** IT IS KNOW BY THIS OFFICE THAT |
| | PREVIOUS HOUSES ALONG THIS SAME ROADWAY |
| | WERE PERHAPS DONE THIS WAS , HOWEVER MAY |
| | NOT HAVE BEEN CORRECT. |
| | |
| | 8) NOTE: PLEASE SEE AS SOME OF THE |
| | COMMENTS WERE REPEAT COMMENTS, PLEASE |
| | SEE FS 553.80(2)(B). THIS IS ONLY GIVEN |
| | A A NOTICE AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |