| 2006-08-04 00:00:00 | ******** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE SEE PANELS FOR ALL |
| | BRANCH CIRCUITS MAY NOT BE LOCATED IN |
| | GARAGE. PLEASE SEE 225.31-225.39. FBC |
| | DEFINITIONS OF ONE BUILDING ETC. |
| | PLEASE SEE DEISGN AS SHOWN NEEDS TO BE |
| | RE-DESIGNED. |
| | |
| | 2) NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM WHICH IS NOT SHOWN FOR |
| | HOUSE. |
| | |
| | 3) NOTE: PLEASE SEE PANEL SCHEDULE IS |
| | NOT COMPLETE FOR ALL A/C LOADS, OCP, AND |
| | CONDUCTOR SIZES. |
| | PLEASE CORRELATE WITH MECH PLANS. |
| | UNABLE TO VERIFY AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE PLANS SHALL ALSO |
| | REFELCT THE 2002 NFPA-72 . |
| | PLEASE SEE LOCATIONS OF SD'S REQUIRED |
| | WITHIN 3' OF THE PEAK ON SLOPED CEILING. |
| | 11.8.3 |
| | |
| | 5) NOTE: PLEASE SEE 408.4,PANEL SCHEDULE |
| | SHALL BE SPECIFIC FOR ALL CIRCUITS, |
| | AREAS/ ROOMS ON PLANS. IE; LIVING RM |
| | LTS, HALL LTS, KTICHEN LTS ETC. |
| | IT IS KNOWN, THAT DURING CONSTRUCTION |
| | THESE WILL MOST LIKELY CHANGE, HOWEVER |
| | THESE CAN BE REVISED AT A LATER DATE |
| | WITH ANY OTHER REVISONS. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE CLARIFY ONLY TWO ARC |
| | FAULT PROTECTED CIRCUITS ARE BEING |
| | SHOWN, YET THERE ARE MORE THAN TWO |
| | BEDRMS. |
| | 210.12B, PLEASE INDICATE OTHER AS |
| | CIRCUITS AS SHOWN APPEAR LOADS FOR ALL |
| | BEDRMS MAY EXCEED BRANCH CIRCUIT RATING. |
| | 240.4, 210.20, 220 |
| | |
| | 7) NOTE: PLEASE SEE NO DINING RM IS |
| | BEING SHOWN, HOWEVER PLEASE SEE |
| | BREAKFAST ARE IS ALSO CONSIDERED TO BE |
| | PART OF THE CIRCUITING AS REQUIRED PER |
| | 210.11C1,210.52B1,220.16. |
| | DINING, BRKFST AREAS AND THE LIKE SHALL |
| | BE ON ONE OR MORE OF THE REQUIRED. ETC. |
| | |
| | 8) NOTE: PLEASE VERIFY THE DISOCNNECTING |
| | MEANS FOR AHUS', AS THEY DO NOT MEET |
| | 110.26. |
| | IF DISCONNECTING MEANS IS PART OF UNIT, |
| | PLEASE SHOW. |
| | |
| | 9) NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | REQUIRED FOR ALL STRUCTURES WHICH |
| | CONTAIN THE ELECTRICAL. |
| | PLEASE SEE 250.50,250.32 ETC |
| | |
| | 10) NOTE: PLEASE SEE LT ABOVE WASHER AND |
| | DRYER DOES NOT SEEM TO MEET 410.8 |
| | PLEASE SEE SHELVING IS COMMON ABOVE |
| | THESE UNITS, AND SPACE FROM 410.8 |
| | REQUIRES 18" OUT ETC. |
| | PLEASE SEE LT MAY BE ABLE TO BE MOUNTED |
| | ABOVE DOOR/ WALL. |
| | |
| | ** PLEASE KNOW, DUE TO THE DEISGN OF |
| | ELECTRICAL SYSTEM AND SUBSTANTIAL |
| | CHANGES WHICH WILL BE REQUIRED. THERE |
| | MAY BE COMMENTS ON NEXT REVIEW. |
| | |
| | ** IMPORTANT ** |
| | PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. ONLY ONE SET OF THE |
| | OLF/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |