| 2006-08-08 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING PLAN REVIEW ON THE SANITARY |
| | PLUMBING RISER DIAGRAM ON SHEET A-4.1, |
| | DETAIL #7.(NOTE: THE FOLLOWING CORREC- |
| | TIONS ARE IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL.) |
| | |
| | 1. PER FBC-2004, CHAPTER 1, SECTION |
| | 106.3.5.4 RESIDENTIAL (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL |
| | WASTE, VENTS, TRAPS WITH SIZES, AND |
| | CLEANOUT LOCATIONS.(NOTE: 2ND FLOOR |
| | LAUNDRY TRAY ROOM #09 MISSING AND NOT |
| | ALL FIXTURE TRAPS SIZED.) |
| | 2. PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | (NOTE: THE 1ST FLOOR POWDER ROOM #04 AND |
| | THE 2ND FLOOR LAUNDRY ROOM #09 SANITARY |
| | ARE PIPED WRONG.) |
| | 3. PER FBC-2004 PLUMBING THE FOLLOWING |
| | NEEDS TO BE CORRECTED ON THE WASHING |
| | MACHINE. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER.(NOTE: WASTE STACK SIZED WRONG) |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE |
| | INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. (NOTE: PLEASE INDICATE |
| | STANDPIPE ON DRAWING) |
| | 4. PER FBC-2004 PLUMBING THE FOLLOWING |
| | NEEDS TO BE INDICATED ON CLEANOUTS. |
| | (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK. PLEASE INDICATE ON |
| | DRAWING. |
| | 5.PER FBC-2004 PLUMBING, SECTION 802.1.6 |
| | DOMESTIC DISHWASHING MACHINES: SHALL |
| | DISCHARGE INTO A WYE-BRANCH FITTING ON |
| | THE TAILPIECE OF THE KITCHEN SINK OR THE |
| | DISHWASHER CONNECTION OF A FOOD WASTE |
| | GRINDER. PLEASE REFERENCE ISOMETRIC |
| | DRAWING. |
| | 6. PER FBC-2004 PLUMBING, SECTION 905.5 |
| | HEIGHT ABOVE FIXTURES: A CONNECTION |
| | BETWEEN A VENT STACK OR STACK VENT SHALL |
| | BE MADE AT LEAST 6" INCHES ABOVE THE |
| | FLOOD LEVEL RIM OF THE FIXTURE SERVED BY |
| | THE VENT.(NOTE: VENT FOR 1ST FLOOR |
| | POWDER ROOM #04 WRONG) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |