| 2006-08-11 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION |
| | |
| | 2) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION THAT |
| | HAVE BEEN REVIEWED AND APPROVED BY THE |
| | DESIGNER OF RECORD |
| | |
| | 4) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | |
| | 5) AN ENGINEER PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS SHALL |
| | INDICATE THEIR NAME AND LICENCE #, AS |
| | WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| | OF AUTHORIZATION #ON EACH SHEET PER |
| | 61G15-23.002 (2) FAC |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 6) THE FOLLOWING PRODUCT APPROVALS |
| | REQUIRE CORRECTIONS |
| | |
| | A) SINGLE I/S ENTRY DOOR IS NOT APPROVED |
| | UNDER THE 2004 STATE PRODUCT |
| | APPROVALS.PLEASE SEE THAT THE ONLY STEEL |
| | EDGE DOOR DOES NOT HAVE IMPACT RATING |
| | BUT FIBERGLASS IMPACT DOORS ARE UNDER FL |
| | #4334 |
| | B) NO PRODUCT APPROVALS WERE SUBMITTED |
| | FOR SLIDING GLASS DOOR |
| | C) PROVIDE UPDATED PRODUCT APPROVALS FOR |
| | ROOF COVERING (NOA HAS BEEN REVISED) |
| | D) "WINDLOAD 188" OVERHEAD GARAGE DOOR |
| | NOT LISTED ON STATE, WILL ACCEPT |
| | MIAMI-DADE FOR LOCAL PRODUCT APPROVAL |
| | E) PROVIDE PRODUCT APPROVALS FOR PRE |
| | CAST LINTELS AND WOOD CONNECTORS/ANCHOR |
| | (FOR CONNECTORS INDEX WITH FL#'S IS |
| | ADEQUATE SEE ATTACHED INDEX COVER) |
| | F) PROVIDE INSTALLATION SCHEDULE, KEY |
| | PLAN AND PRODUCT APPROVALS FOR IMPACT |
| | PROTECTIVE SHUTTERS |
| | |
| | 7) REMOVE ALL NON USED PRODUCT APPROVAL |
| | FROM SUBMITTALS |
| | |
| | 8) PROVIDE A SITE PLAN THAT SHOWS |
| | DRAINAGE IN COMPLIANCE WITH THE |
| | REQUIREMENTS OF R403.1 |
| | |
| | 9) ROOF SHEATHING NAIL PATTERN ON S-3 TO |
| | MEET THE REQUIREMENTS OF 2304.9.1 FBC |
| | |
| | 10) PROVIDE CONNECTORS AND UPLIFT FOR |
| | PATIO ROOF TRUSSES ON S-2 |
| | |
| | 11) DOOR BETWEEN HOUSE AND GARAGE SHALL |
| | MEET THE REQUIREMENTS OF R309.1 FBC |
| | |
| | 12) WINDOW ABOVE TUB DECK AND ANY |
| | GLAZING BETWEEN TUB AND SHOWER SHALL BE |
| | CONSIDERED GLAZING IN A HAZARDOUS |
| | LOCATION PER R308.4 PLEASE SPECIFY |
| | TEMPERED GLASS ON DRAWINGS |
| | |
| | 13) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |