Plan Review Notes
Plan Review Notes For Permit 06080064
Permit Number 06080064
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-05 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 1} THE "SITE PLAN " THAT WAS REQUESTED
 IN THE PREVIOUS REVIEW DOES NOT SHOW A
 DISCONNECTING MEANS AT THE NEAREST POINT
 OF ENTRANCE OF THE CONDUCTORS FROM THE
 GENERATOR, NOR DOES THE RISER.
  
 2} PLEASE SUBMIT A SITE PLAN AND LOCATE
 ALL THE SERVICE AND GENERATOR GEAR ON
 SAME SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW