| Notes |
| Date |
Text |
| 2006-09-05 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL FOR THE GENERATOR, EQUIPMENT | | | (TRANSFER SWITCHES, PANELS ETC.) | | | AND PAD PER 108.3 FBC AS AMENDED. | | | INCREASE THE VALUE AT THE COUNTER WHEN | | | RESUBMITTING, AND GET A RECEIPT FROM THE | | | PERMIT CLERK. | | | | | | 1} THE "SITE PLAN " THAT WAS REQUESTED | | | IN THE PREVIOUS REVIEW DOES NOT SHOW A | | | DISCONNECTING MEANS AT THE NEAREST POINT | | | OF ENTRANCE OF THE CONDUCTORS FROM THE | | | GENERATOR, NOR DOES THE RISER. | | | | | | 2} PLEASE SUBMIT A SITE PLAN AND LOCATE | | | ALL THE SERVICE AND GENERATOR GEAR ON | | | SAME SO THAT COMPLIANCE WITH | | | 230.72(GROUPING), 225.31-39 FOR THE | | | DISCONNECTING MEANS REQUIREMENTS AND | | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | | | | | | WILLIAM R TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/561) 805-6731 | | | | | | |
|