| 2007-01-07 10:54:32 | ** UNSAT 3RD REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE PROVIDE CALCULATIONS AS REQUESTED ON |
| | THE TWO PREVIOUS REVIEWS. RESPONSE LETTER MENTIONS TO |
| | SEE SHEET A-7, HOWEVER SHEET A-7 ONLY SHOWS THE PANEL |
| | SCHEDULE AND SOME CONNECTED LOADS. PLEASE SEE 220.3, |
| | 220.10, 220.11 220.13 ETC |
| | ALL CONTINUOUS LOADS PER 215.3, 230.42 |
| | |
| | 2) NOTE:PLEASE SEE 220.3(B)(7) AND 220.12(A) FOR |
| | INFORMATION REGARDING LOAD COMPUTATIONS FOR SHOW |
| | WINDOWS. PLEASE SEE HOW LOADS SHALL BE FIGURED FOR |
| | BRACNH CIRCUITS AND FOR FEEDERS. PLEASE SEE THERE IS NO |
| | BREAK DOWN OR INFORMATION REGARDING LOADS ON WINDOWS |
| | AND HOW THESE LOADS WERE DERIVED. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW AS THE 2ND SET OF |
| | PLANS WHICH CAME IN CONTAIN A COMPLETELY NEW RISER |
| | THERE WERE NEW COMMENTS. PLEASE SEE THAT IS WAS |
| | REQUESTED TO SUBMIT THE MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE EMERGENCY PANEL/MTS WHICH WAS BEING INSTALLED. |
| | PLEASE SEE THERE ARE SPEC SHEETS IN THE PACKAGE HOWEVER |
| | THEY ARE FOR COUNTLESS PANELS AND EQUIPMENT. PLEASE |
| | ONLY SUBMIT THAT WHICH CORRELATES TO PLANS AND THAT |
| | WHICH IS RELEVANT TO THIS INSTALLATION. PANELS AND |
| | SPECS FOR ALL THE OTHERS AS SUBMITTED WILL HAVE NO |
| | BEARING ON THIS JOB. |
| | 110.3, 90.7. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW FOR REQUIRED |
| | DISCONNECTING MEANS FOR THE FEED FROM THE GEN.IF IN |
| | AN EMERGENCY THE GENERATOR IS RUNNING AND CAN NOT BE |
| | SHUT OFF, WHEN MAINS AND DISCONNECTING MEANS ARE NOT |
| | GROUPED, UNPLUGGING THE GENERATOR WHILE UNDER LOAD IS |
| | NOT PERMITTED AND IS A SAFETY ISSUE FOR ANY PERSONNEL. |
| | PLEASE SEE NOTE#7 ON A-6 STILL MENTIONS ALL ELECTRICAL |
| | PANELS AND SERVICEEQUIPMENT IS EXISTING, YET PLANS |
| | SHOW MANY OF THESE ITEMS AS NEW? |
| | PLEASE CORRELATE NOTES, PLANS, RISER, PANELS ETC. |
| | 225.31-225.39, 230.72 |
| | |
| | 5) NOTE: PLEASE KNOW IT HAS BEEN DISCOVERED SINCE THE |
| | LAST REVIEW THIS IS A BUILD OUT OF WHAT USED TO BE AN |
| | OLD SERVICE GARAGE AND WOULD BE A CHANGE IN OCCUPANCY. |
| | |
| | PLEASE SUBMIT ENERGY CALCULATIONS PER 2004 FBC. |
| | 13-415.1.AB.1 |
| | THIS WAS NOT PREVIOUSLY REQUESTED AS THIS WAS APPLIED |
| | AS EXISTING CAR SALES OFFICE AND EXISTING TENANT FOR |
| | SAME USE. |
| | |
| | 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO |
| | FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. PLEASE SEE A FEE OF $2100.00 HAS NOW |
| | BEEN ASSESSED TO THE DESIGN PROFESSIONAL AS REQUIRED |
| | PER THE FLORIDA STATUTES AS GIVEN. THIS FEE IS BEING |
| | ADDED TO THEEXISTING 4X FEE FOR STARTING WORK WITHOUT |
| | PERMITS WHICH WAS ALREADY ADDED TO THIS JOB. PLEASE SEE |
| | THIS FEE IS REQUIRED TO BE PAID BEFORE RESUBMITTING OF |
| | PLANS FOR THE NEXT REVIEW. PLEASE ALSO KNOW ONE SET OF |
| | EACH OF THE PLANS ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |