| Plan Review Notes For Permit 06080061 |
| Permit Number |
06080061 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-02 18:49:37 | --------------------DENIED----------------- | | | | | | FBC 2004 | | | FBC,EB 2004 | | | FBC,M 2004 | | | | | | 1. PER FBC,EB SEC.609.1, PLEASE SHOW COMPLIANCE WITH | | | VENTILATION REQUIREMENTS OF FBC,M SEC.402 OR 403. | | | | | | 2. PER FBC,EB SEC.509.1 ANY COMPONENT OF THE EXISTING | | | A/C SYSTEM SHOWN TO BE DEFECTIVE SHALL BE REPAIRED OR | | | REPLACED - FBC,M 301.11 | | | | | | 3. CAR RENTAL AREA SHOWS NEW R/A GRILL IN CEILING WITH | | | NO DUCT ATTACHED. PLAN NOTE SAYS ALL RETURNS TO BE | | | DUCTED. THIS R/A GRILL MAY BE DELETED DUE TO FREE FLOW | | | RETURN BACK TO THE 48X36 CENTRALIZED RETURN IN THE | | | VESTIBULE. | | | | | | 4. THE TWO 12" ROUND R/A JUMPERS DO NOT MEET THE | | | BALANCED RETURN EXCEPTIONS OF FBC,M 601.4.UNLESS THE | | | DUCTS ARE DESIGNED TO MEET THE EXCEPTIONS, A FIELD TEST | | | WILL BE REQUIRED AT FINAL INSPECTION TO SHOW COMPLIANCE | | | WITH THE MAXIMUM ALLOWABLE PRESSURE DIFFERENTIAL OF | | | THIS SECTION (0.01" WC). | | | | | | 5. PG A1 DETAIL #5 - ROOF INSULATION SHALL NOT BE | | | INSTALLED ON A SUSPENDED CEILING WITH REMOVABLE CEILING | | | PANELS PER FBC SEC. 13-404.1.ABC.1.SEE SEC. 13-B-1.3 | | | FOR INSULATION INSTALLATION REQUIREMENTS. | | | | | | REVIEWED BY: | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|