| 2006-10-28 17:16:06 | ***UNSAT 2ND REVIEW** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| | NEW NOTES DUE TO COMPLETE CHNAGE IN THE SERVICE AS NOW |
| | SUBMITTED. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH NEW NOTES ADDED TO THE BOTTOM. |
| | |
| | 1) NOTE:NO, SAME NOTE. |
| | RESPONSE MENTIONS TO SEE 6 AND 7, HOWEVER NOT COMPLETE |
| | FOR NEW PANEL EM AS THE LOADS ARE NOT EVEN SHOWN AND |
| | COULD NOT LOCATE ANY LOAD CALCULATIONS FOR SERVICE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE CALCULATIONS FOR |
| | EXISTING SERVICE PER 220.3,220.10,220.11 |
| | 220.13 ETC |
| | ALL CONTINUOUS LOADS PER 215.3,230.42 |
| | |
| | 2) NOTE: NO/OK, RECEPTS ADDED, HOWEVER LOADS AND LOADS |
| | IN CALCULATIONS NOT SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.62, FOR MISSING |
| | SHOW WINDOWS OUTLETS REQUIRED ABOVE |
| | WINDOWS. |
| | "TO DISCOURAGE FLOOR RECEPTACLES AND |
| | UNSIGHTLY EXTENSION CORDS LIKELY TO |
| | CAUSE PHYSICAL INJURY, RECEPTACLES MUST |
| | BE INSTALLED DIRECTLY ABOVE A SHOW |
| | WINDOW, AND ONE RECEPTACLE IS REQUIRED |
| | FOR EVERY 12 LINEAR FT OR ?MAJOR |
| | FRACTION THEREOF? (6 FT OR MORE). SEE |
| | 220.3(B)(7) AND 220.12(A) FOR |
| | INFORMATION REGARDING LOAD COMPUTATIONS |
| | FOR SHOW WINDOWS." |
| | |
| | 3) NOTE:OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | *** NEW NOTE DUE TO COMPLETLY NEW RISER SUBMITTED. ** |
| | |
| | 5) NOTE: PLEASE SEE A NEW MTS PANEL IS BEING SHOWN, |
| | HOWEVER PLEASE SUBMIT MANUFACTURES SPACES/CUT SHEETS |
| | FOR THIS PANEL/ MTS. |
| | PLEASE SEE THIS UNIT ON RISER DOES NOT CORRELATE WITH |
| | THE EM AS SHOWN ON SHEET 7. |
| | 110.3,90.7, 225.31-225.39 ETC |
| | |
| | 6) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS FOR |
| | POWER FROM GEN, OR-THE MTS IS TO BE LOCATED OUTSIDE, OR |
| | THERE ARE NUMEROUS OTHER SCENARIOS WHICH CAN BE DONE . |
| | PLEASE SEE NOTE ABOVE. |
| | |
| | 7) NOTE: PLEASE SEE NOW A RISER IS BEING SUBMITTED, |
| | HOWEVER PLEASE LABEL AND CORRELATE ALL EQUIPMENT AND |
| | SIZES FROM PANELS TO RISER. PLEASE COMPLETE RISER |
| | DIAGRAM WITH ALL CONDUCTORS AND THE CORRECT AMOUNT. |
| | PLEASE SEE RISER SHOWS SEC'S, HOWEVER THE # OF |
| | CONDUCTORS DO NOT ADD UP??? |
| | PLEASE SEE THE FEEDERS FOR THE PANEL "A" ARE NOT SHOWN |
| | ON RISER , HOWEVER NOTED ON PANEL "A" AS EXISTING 150A |
| | RATED?PLEASE EXPLAIN THIS AS THE RISER NOW INDICATES |
| | NEW 200A FUSES FEEDING THE EXISTING 150A FEEDERS. |
| | PLEASE COMPLETE RISER. 240.4,310.16, 215.5 ETC |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE MISPRINT FOR THE EQUIPMENT |
| | GROUNDING CONDUCTOR ON PANEL "EM", SHOWS #60 FOR #6. |
| | |
| | 9) NOTE: PLEASE SEE COLOR CODING SHALL BE BLACK, |
| | ORANGE, RED. IF INDEED AS NOTED. PLEASE SEE LABELING OF |
| | 277/480 CAN NOT BE "ORANGE" ON "B" PHASE, IF CODE |
| | REQUIRES ORANGE FOR A "HIGH-LEG" 277/480V SYSTEMS ARE |
| | NOT "HIGH-LEGS". |
| | PLEASE ADJUST. |
| | 300. |
| | |
| | 10) NOTE; PLEASE SHOW LOCATION OF RECEPT AND NEMA |
| | RATING. PLEASE SUBMIT SPEC ON RECEPT FOR WP LOCATION. |
| | 110.3,90.7. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 11) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED |
| | TO NOTED WITH RESPECT TO REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN ATTHIS TIME. |
| | |
| | |
| | ** PLEASE KNOW, AS RISER HAS MANY COMMENTS, PLEASE |
| | ADDRESS ALL. |
| | PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN |
| | SUBMITTED THERE MAY BE COMMENTS ON NEXT REVIEW. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |