| 2006-11-09 16:57:29 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. PRODUCT APPROVALS HAVE NOT |
| | BEEN APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 3)SUBMIT ENERGY CALCULATIONS AND FORMS AS REQUIRED BY |
| | FBC 13-101.1.3 FOR RENOVATED COMMERCIAL BUILDINGS. |
| | ADDITIONAL CONDITIONED SPACE IS BEING ADDED THAT WAS |
| | PREVIOUSLY UNCONDITIONED. (2 COPIES) |
| | |
| | 4) ALL DOORS REQUIRED TO BE ACCESSIBLE BY FBC 11-4.1.6 |
| | ARE REQUIRED TO HAVE HARDWARE WHICH COMPLIES WITH |
| | 11-4.13.9. THE NOTES ON THE DOOR SCHEDULE DO NOT |
| | ADDRESS ALL OF THE DOORS THAT ARE REQUIRED TO BE |
| | ACCESSIBLE. |
| | |
| | 5) THE STOREFRONT SHOP DRAWINGS FROM THE ENGINEER |
| | (THOMAS J. TWOMEY) ARE REQUIRED TO BE SIGNED AND |
| | SEALED. SEE FAC 61G15-23.002 AND CHAPTER 471, F.S. |
| | |
| | 6) THE CODE SECTION FOR THE REQUIRED ACCESSIBLE COUNTER |
| | IS INCORRECTLY LISTED AS 11-4.33. THE CORRECT SECTION |
| | IS FBC 11-7.2(2). ALSO AN AUXILIARY COUNTER NOT TABLE |
| | IS REQUIRED AS ONE OPTION. PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |