| Plan Review Notes For Permit 06080061 |
| Permit Number |
06080061 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-25 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT D-1 IN THE INSTALLATION OR | | | REMOVAL OF ANY PART OF A DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | SECTION 704.5. INDICATE WHERE THE | | | SANITARY PIPING WILL BE ABANDONED. POINT | | | OF ABANDONMENT SHALL NOT BE COVERED | | | PRIOR TO INSPECTIONS. | | | | | | 2. SHT A-1 CAR PREPARATION AREA DRAIN | | | MAY BE REQUIRED TO CONNECT TO A SAND/OIL INTECEPTOR. | | | PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE | | | MANAGER. (561) | | | 822-2271, (561 822-2279(FAX), OR E-MAIL | | | [email protected]. | | | | | | 3. SHT A-5 WATER RISER DIAGRAM. THE | | | WATER HAMMER ARRESTORS PROVIDED SHALL BE | | | LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE", NOT IN THE CEILING AS | | | SHOWN. PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. | | | | | | 4. SHT A-5 WATER RISER DIAGRAM. FULL | | | OPEN VALVES SHALL BE INSTALLED ON THE | | | TOP OF EVERY WATER DOWN-FEED PIPE. | | | SECTION 606.1(4). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|