| Plan Review Notes For Permit 06080061 |
| Permit Number |
06080061 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-06 00:00:00 | *****DENIED***** | | | | | | | | | | | | | | | 1.) NFPA 101,2003 EDITION, AND FLORIDA | | | FIRE PREVENTION CODE,2004 SHALL BE | | | REFERENCED. | | | | | | 2.) CONSTRUTION, ALTERATION, AND | | | DEMOLITION OPERATIONS TO COMPLY WITH | | | NFPA 241. | | | | | | 3.) ON SHEET A-1, SHOW HOW THE NUMERICAL | | | ADDRESS WILL BE DISPLAYED. AS PER WEST | | | PALM BEACH CODE, NUMERICAL ADDRESS SHALL | | | BE NO LESS THAN 6" IN HEIGHT AND 1" IN | | | WIDTH VISIBLE FROM SOUTH DIXIE HIGHWAY. | | | | | | 3.) INTERIOR FINISH, WALLS, AND CEILING | | | (IN A NON-SPRINKLERED BUILDING) SHALL BE | | | CLASS "A" OR CLASS "B". | | | | | | 4.) IF THE SCOPE OF THE INTERIOR WORK | | | INCLUDES THE ADDITION OR MODIFICATION OF | | | THE FIRE PROTECTION SYSTEM, SEPARATE | | | PERMIT AND SHOP DRAWINGS/PLANS ARE | | | REQUIRED. | | | | | | 5.) ON SHEET D-1, TWO EXITS ARE STATED. | | | ONLY ONE EXIT IS SHOWN ON THE PLANS, | | | WHERE IS THE SECOND EXIT? | | | | | | | | | | | | CAPTAIN MICHAEL A. WILLIAMS | | | FIRE PREVENTION REVIEW | | | 561-805-6722 |
|