Plan Review Notes
Plan Review Notes For Permit 06080053
Permit Number 06080053
Review Stop B
Sequence Number 2
Notes
Date Text
2006-09-29 00:00:00DENIED BY BUILDING
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT ENERGY CALULATION FORMS AS
 REQUIRED BY FBC 13-101.2.
  
 3) WPB ADMINISTRATIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. A STAMP IS
 NOT ACCEPTABLE, THEY MUST BE SIGNED BY
 DOR.
  
 4) THE PRODUCT APPROVAL STATE COVER
 SHEET FOR THE STORM PANELS IS FOR THE
 2001 CODE. THE ONE FOR THE 2004 FBC IS
 FL 7226 AND THE UPDATED ACOMPANYING NOA
 IS NOA NO 05-926.02. SUBMIT THE CURRENT
 PRODUCT INFORMATION.
  
 5) THE UPDATED NOA FOR THE 2100 SERIES
 SINGLE HUNG WINDOWS WITH FL 6585 IS NOA
 NO 05-0729.03. SUBMIT THE CURRENT
 PRODUCT INFORMATION.
  
 6) R303.3 BATHROOMS, WATER CLOSET
 COMPARTMENTS AND OTHER SIMILAR ROOMS
 SHALL BE PROVIDED WITH AGGREGATE GLAZING
 AREA IN WINDOWS OF NOT LESS THAN 3
 SQUARE FEET (0.279 M 2 ), ONE-HALF OF
 WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE
 REQUIRED WHERE ARTIFICIAL LIGHT AND A
 MECHANICAL VENTILATION SYSTEM ARE
 PROVIDED. THE MINIMUM VENTILATION RATES
 SHALL BE 50 CFM (23.6 L/S) FOR
 INTERMITTENT VENTILATION OR 20 CFM (9.4
 L/S) FOR CONTINUOUS VENTILATION.
 VENTILATION AIR FROM THE SPACE SHALL BE
 EXHAUSTED DIRECTLY TO THE OUTSIDE.
 BECAUSE THE BATHROOM NO LONGER WILL HAVE
 A WINDOW OPENING TO THE EXTERIOR A
 MECHANICAL VENT WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  