| 2006-09-29 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT ENERGY CALULATION FORMS AS |
| | REQUIRED BY FBC 13-101.2. |
| | |
| | 3) WPB ADMINISTRATIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. A STAMP IS |
| | NOT ACCEPTABLE, THEY MUST BE SIGNED BY |
| | DOR. |
| | |
| | 4) THE PRODUCT APPROVAL STATE COVER |
| | SHEET FOR THE STORM PANELS IS FOR THE |
| | 2001 CODE. THE ONE FOR THE 2004 FBC IS |
| | FL 7226 AND THE UPDATED ACOMPANYING NOA |
| | IS NOA NO 05-926.02. SUBMIT THE CURRENT |
| | PRODUCT INFORMATION. |
| | |
| | 5) THE UPDATED NOA FOR THE 2100 SERIES |
| | SINGLE HUNG WINDOWS WITH FL 6585 IS NOA |
| | NO 05-0729.03. SUBMIT THE CURRENT |
| | PRODUCT INFORMATION. |
| | |
| | 6) R303.3 BATHROOMS, WATER CLOSET |
| | COMPARTMENTS AND OTHER SIMILAR ROOMS |
| | SHALL BE PROVIDED WITH AGGREGATE GLAZING |
| | AREA IN WINDOWS OF NOT LESS THAN 3 |
| | SQUARE FEET (0.279 M 2 ), ONE-HALF OF |
| | WHICH MUST BE OPENABLE. |
| | EXCEPTION: THE GLAZED AREAS SHALL NOT BE |
| | REQUIRED WHERE ARTIFICIAL LIGHT AND A |
| | MECHANICAL VENTILATION SYSTEM ARE |
| | PROVIDED. THE MINIMUM VENTILATION RATES |
| | SHALL BE 50 CFM (23.6 L/S) FOR |
| | INTERMITTENT VENTILATION OR 20 CFM (9.4 |
| | L/S) FOR CONTINUOUS VENTILATION. |
| | VENTILATION AIR FROM THE SPACE SHALL BE |
| | EXHAUSTED DIRECTLY TO THE OUTSIDE. |
| | BECAUSE THE BATHROOM NO LONGER WILL HAVE |
| | A WINDOW OPENING TO THE EXTERIOR A |
| | MECHANICAL VENT WILL BE REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |