| 2006-08-15 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004, SEC. 424.2 OR |
| | FBRC-2004, SEC.4101 SWIMMING POOLS: |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING PLAN REVIEW: |
| | |
| | 1. PLEASE CORRELATE THE 400,000 GAS |
| | HEATER INDICATED ON SHEET 1 SPECIFICA- |
| | TIONS WITH THE PIPING SCHEMATIC ON SHEET |
| | 2. THE PIPING SCHEMATIC ON SHEET 2 DOES |
| | NOT INDICATE THE GAS HEATER, PLEASE |
| | INDICATE THE GAS HEATER ON THE |
| | RESUMITTAL. |
| | 2. PLEASE SUBMIT MANUFACTURER CUT SHEETS |
| | OF THE 400,000 BTU GAS HEATER THAT |
| | CONFORMS WITH THE FOLLOWING. |
| | (A) FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | (B) FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |