| Notes |
| Date |
Text |
| 2006-08-11 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE #12 CONDUCTORS FEEDING THE HEAT PUMP | | | ON THE SCHEMATIC ARE TOO SMALL FOR THE | | | 50 AMP LOAD SERVED. 310.16. 2002 NEC | | | | | | PROVIDE A LOAD CALCULATION PER 220.31, | | | INCLUDE ADDED LOADS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|