Plan Review Notes
Plan Review Notes For Permit 06080009
Permit Number 06080009
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-11 00:00:00 
  
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE #12 CONDUCTORS FEEDING THE HEAT PUMP
 ON THE SCHEMATIC ARE TOO SMALL FOR THE
 50 AMP LOAD SERVED. 310.16. 2002 NEC
  
 PROVIDE A LOAD CALCULATION PER 220.31,
 INCLUDE ADDED LOADS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW