Plan Review Notes
Plan Review Notes For Permit 06071960
Permit Number 06071960
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-08-07 00:00:00***UNSAT***
  
  
 1.) PLEASE BE ADVISED THAT SHOP
 DRAWINGS/PLANS ARE TO HAVE THE
 ENGINEERED SEAL WITH WORDING "LICENSE"
 IN LIEU OF "CERTIFICATE".
  
 2.) AREA 3 SHOWS A SAFETY MARGIN OF ONLY
 3.08 PSI. AS PER WPBFR, A SAFETY MARGIN
 OF AT LEAST 5.0 IS REQUIRED.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722