| 2006-08-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A-1 WOMENS AND MENS RESTROOMS |
| | INDICATE ADA COMPLIANT STALLS. THESE ARE |
| | NOT COMPLIANT WITH FBC-2004 CHAPTER 11 |
| | SECTION 11-4.17.3 EXCEPTION (1). SEE |
| | FIGURE 30E FOR CORRECT LAYOUT OF |
| | REQUIRED STALL. |
| | |
| | 2. SHT A-4 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE RESTROOMS: |
| | FOR THE W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | FOR THE UNINAL |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | FOR THE LAVS |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 3. SHT A-4 PER SECTION 1210.2 |
| | WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| | OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| | EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. |
| | PLEASE INDICATE HOW MR GYPSUM WALL BOARD |
| | COMPLIES WITH THESE REQUIREMENTS. |
| | |
| | 4. SHT P-2 WATER ISOMETRIC. A WATER |
| | HAMMER ARESTOR IS REQUIRED AT THE DISH |
| | WASHER. 604.9. |
| | |
| | 5. SHT P-2 SANT. ISOMETRIC. SHOW ALL |
| | PIPE SIZES TO THE W/C'S. SECTION |
| | 106.1.1. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |