| Plan Review Notes For Permit 06071887 |
| Permit Number |
06071887 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-07 00:00:00 | ******* PROVISO/ REVISION ********** | | | | | | 1) NOTE: PLEASE CORRELATE HEAT LOADS | | | WITH MECHANICAL PLANS AS PREVIOULSY | | | REQUESTED ON 1ST REVIEW. PLEASE SEE ALL | | | AHU'S ON MECHANICAL PLANS INDICATE 10KW | | | FOR EACH , HOWEVER ELECTRICAAL PLANS | | | SHOW AHU #2 AS 5KW WITH #6AWG?? | | | PLEASE ALSO SEE LOAD CALCULATIONS ALSO | | | DO NOT INCLUDE INCREASED LOAD. | | | PLEASE SEE 310.16,240.4,424.3B | | | | | | 2) NOTE: PLEASE SEE CU#2, AS PANEL | | | SCHEDULE SHOWS 40A OCP ON #12 AWG. | | | PLEASE SEE 310.16, 240.4 MINIMUM SIZE TO | | | BE #8. | | | | | | ** PLEASE KNOW, THE ABOVE NOTE MUST BE | | | ADDRESSED, REVISED, SUBMITTED FOR | | | REVIEW, STAMPED AND ON JOBSITE "BEFORE | | | ROUGH ELECTRICAL INSPECTION" IS | | | SCHEDULED ALONG WITH ANY OTHER | | | ELECTRICAL REVISIONS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE ON CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|