| 2006-08-04 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED |
| | ON THE ISOMETRIC PLUMBING RISER DIAGRAM |
| | ON SHEET A-6 FOR PLUMBING PLAN REVIEW: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL. NOTE: SHEET A-6 |
| | ISOMETRIC PLUMBING RISER DOES NOT |
| | REFLECT THE FLOOR PLAN IT INDICATES AN |
| | EXTRA HALF BATH NOT INDICATED ON THE |
| | FLOOR PLAN SHEET A-2. PLEASE SEE SHEET |
| | A-6 CORRECTED PLMG. RISER DRAWING IN RED |
| | INK FOR REFERENCE FOR RESUBMITTAL. |
| | 2. IN BATH 3 THE LAVATORY IS INDICATED |
| | WRONG. PLEASE REFERENCE THE CORRECTED |
| | DRAWING IN RED INK ON SHEET A-6 FOR |
| | RESUBMITTAL. |
| | 3. RELIEF VENTS ARE REQUIRED FOR THE |
| | SHOWER IN "HIS BATH" AND THE W.POOL IN |
| | "HER BATH" PER FBC-2004 PLMG. TABLE |
| | 906.1 AND SEC. 911.4 RELIEF VENT. PLEASE |
| | REFERENCE THE CORRECTED DRAWING IN RED |
| | INK ON SHEET A-6 FOR RESUBMITTAL. |
| | 4. A VENT IS REQUIRED FOR THE BIDET IN |
| | "HER BATH" PER FBC-2004 PLMG. |
| | SEC.901.2.1. PLEASE REFERENCE THE |
| | CORRECTED DRAWING IN RED INK FOR |
| | RESUBMITTAL. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |