| 2006-08-02 00:00:00 | ****** UNSAT ***** |
| | |
| | |
| | **** IMPORTANT ***** |
| | |
| | PLEASE SEE PERMIT APPLICATION FROM |
| | CONTRACTOR IS IN FACT A COLORED |
| | PHOTO-COPY OF AN ORIGINAL APPLICATION. |
| | PLEASE KNOW ALL SIGNATURES FOR ALL |
| | CONTRACTORS SHALL BE ORIGINAL. THIS IS A |
| | COPY FOR ENTIRE APPLICATION INCLUDING |
| | BACK WITH NOTARY ETC. |
| | THIS PERMIT APPLICATION WILL BE RETAINED |
| | BY THIS OFFICE AND COMPARED TO ALL OTHER |
| | SUBMITTED APPLICATIONS FOR PAST SINGLE |
| | FAMILY HOUSE PLANS SUBMITTED. PLEASE |
| | KNOW, ANY PAST APPLICATIONS FOUND ALSO |
| | TO BE COLORED PHOTO-COPIES WILL REQUIRE |
| | ALL NEWORIGINALS TO BE SUBMITTED. |
| | SUBMITTING DOCUMENTATION WHICH WAS A |
| | COPY OF AN ORIGINAL FOR PERMITTING IN |
| | WHICH THE SUB CONTRACTORS HAVE NOT |
| | SIGNED IS IN VIOLATION OF CONTRACTING |
| | LAWS AND FLORIDA STATUES FOR RECORD OF |
| | LEGAL DOCUMENTATION. PLEASE KNOW THIS |
| | MAY BE TURNED OVER TO THE STATE |
| | LICENSING BOARD. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THT FOLLOWING |
| | CODES ARE REFLECTED ON PLANS. |
| | 2002 NFPA-70 (NEC), NFPA-72 2002. |
| | PLANS DO SHOW ARC FAULT FOR 210.12B PER |
| | 2002, HOWEVER PLANS SHOULD HAVE THE CODE |
| | REFLECTED INTO DESIGN ON COVER SHEET AS |
| | A MINIMUM. |
| | |
| | 2) NOTE: PLEASE HAVE PLANS NOTE SD'S |
| | INSTALLED PER NFPA-72 11.5.1.1, 11.8.3 |
| | PLEASE SEE TWO AREAS ON PLANS REDLINED. |
| | ONE FOR SD LOCATED OUTSIDE GUEST SUITE |
| | IS REQUIRED WITHIN 3' OF THE PEAK ON A |
| | SLOPED CEILING. |
| | PLEASE CALRIFY THE LOCATION OF THE SD |
| | OUTSIDE THE MASTER BEDRM. |
| | PLEASE SEE THIS SEEMS TO BE SHOWN |
| | OUTSIDE HOME THEATRE.? |
| | |
| | 3) NOTE: PLEASE CORRELATE ALL KW |
| | RATINGS FOR HEAT STRIPS IN AHU'S. PLEASE |
| | SEE MECHANICAL PLANS INDICATE ALL UNITS |
| | AS 10KW. IF SO PLEASE SEE 424.3B FOR AHU |
| | #3. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE LOADS ON ANY |
| | CONTINUOUS LOADS IF THEY ARE ALREADY |
| | FIGURED AT 125%. (POOL PUMP, RECIR PUMP) |
| | 215.3,230.42 |
| | |
| | 5) NOTE: PLEASE SEE 408.4, A MIN PANEL |
| | SCHEDULE DENOTING ALL CIRCUITS AND |
| | CORRELATION WITH ROOM AND AREA |
| | DESIGNATIONS IS REQUIRED AT THIS TIME. |
| | PLEASE KNOW, IT IS KNOWN THAT THE |
| | CIRCUITS WILL MOST LIKELY BE REVISED |
| | DURING THE CONSTRUCTION AND MAY BE |
| | REVISED AT A LATER DATE ALONG WITH ANY |
| | OTHER REVISIONS. |
| | PLEASE SEE EXAMPLE. IE: LIVING RM LTS, |
| | MASTER BEDRM RECEPTS, BATH #4 RECEPTS |
| | ETC. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE PLANS FOR MISSING |
| | REQUIRED DISCONNECTING MEANS FOR CU'S. |
| | PLEASE SEE 440.11 AND 110.26 |
| | |
| | 7) NOTE: PLEASE CLARIFY BRANCH CIRCUIT |
| | TO REFRIGERATOR(S). PANEL SCHEDULE |
| | MENTIONS "2" AND ON A 2-POLE BRKR AND |
| | 3KW LOAD?? |
| | PLEASE CLARIFY AS ONLY ONE FRIG IS SHOWN |
| | .? |
| | PLEASE CLARIFY AND ADJUST. |
| | 106.1.2 |
| | |
| | ** BEFORE RESUBMITTING PLANS AND ONCE |
| | ALL REVIEWS ARE DONE. PLEASE BE SURE TO |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT THE NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE SUBMIT ONLY ONE COPY OF |
| | THE OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |