Plan Review Notes
Plan Review Notes For Permit 06071876
Permit Number 06071876
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-21 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE WINDOW IN THE NEW BATHROOM MUST
 COMPLY WITH FBC R308.4 (5). SAFETY
 GLAZING IS REQUIRED IN THE FOLLOWING
 LOCATION.
 5.GLAZING IN DOORS AND ENCLOSURES
 FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM
 ROOMS, BATHTUBS AND SHOWERS. GLAZING IN
 ANY PART OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM
 EXPOSED EDGE OF THE GLAZING IS LESS THAN
 60 INCHES (1524 MM) MEASURED VERTICALLY
 ABOVE ANY STANDING OR WALKING SURFACE.
  
 3) SPECIFY THE NEW WALLS ON THE PLANS.
  
 4) PROVIDE A DETAIL OF NEW WALLS.
 SPECIFY FRAMING MATERIAL, STUD SPACING,
 WALL SHEATHING.
  
 5) SPECIFY THE BATHROOM WALL AND FLOOR
 FINISHES.
  
 6) FBC R303.3BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND
 OTHER SIMILAR ROOMS SHALL BE PROVIDED
 WITH AGGREGATE GLAZING AREA IN WINDOWS
 OF NOT LESS THAN 3 SQUARE FEET (0.279 M
 2 ), ONE-HALF OF WHICH MUST BE OPENABLE.
  
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE
 REQUIRED WHERE ARTIFICIAL LIGHT AND A
 MECHANICAL VENTILATION SYSTEM ARE
 PROVIDED. THE MINIMUM VENTILATION RATES
 SHALL BE 50 CFM (23.6 L/S) FOR
 INTERMITTENT VENTILATION OR 20 CFM (9.4
 L/S) FOR CONTINUOUS VENTILATION.
 VENTILATION AIR FROM THE SPACE SHALL BE
 EXHAUSTED DIRECTLY TO THE OUTSIDE.
 MUST HAVE WINDOW THAT COMPLIES OR
 MECHANICAL VENTILATION.
  
 7) TWO COMPLETE SETS OF PLANS ARE
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  