Plan Review Notes
Plan Review Notes For Permit 06071838
Permit Number 06071838
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-08-17 00:00:00***DENIED***
  
 1) IS THIS AREA PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM?
  
 2) WHERE APPLICABLE, FIRE SPRINKLER
 REMODEL SHALL COMPLY WITH NFPA 13,
 REGARDING RACK AND HIGH PILE STORAGE.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 4) WILL ANY EXISTING FIRE ALARM
 EQUIPMENT BE IMPACTED IN TERMS OF
 VISIBILITY/AUDIBILTY WITH THE
 INTRODUCTION OF RACKS AND STORAGE?
  
 5) PLEASE SHOW THE LOCATIONS OF FIRE
 EXTINGUISHERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722