| 2006-08-09 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE NOTE A DISCONNECT IS REQUIRED |
| | PER 225.31 AND 32. INDICATE LOCATION ON |
| | THE RISER AND SITE PLAN. THE TRANSFER |
| | SWITCH MAY NOT MEET THIS REQUIREMENT, |
| | SEE SPECS BEFORE SUBMITTING. SHOULD BE |
| | LOCATED WHERE THE JUNCTION BOX IS SHOWN. |
| | THIS DISCONNECT IS NOT REQUIRED TO HAVE |
| | OVERCURRENT PROTECTION. |
| | |
| | 2} SUBMIT A SITE PLAN AND LOCATE ALL |
| | THE SERVICE AND GENERATOR GEAR ON SAME |
| | SO THAT COMPLIANCE WITH 230.72 |
| | (GROUPING), 225.31-39 FOR THE |
| | DISCONNECTING MEANS REQUIREMENTS AND |
| | 250.32 FOR GROUNDING CAN BE REVIEWED. |
| | |
| | 3} PROVIDE A LOAD CALCULATION FOR THE |
| | LOAD INTENDED TO BE SERVED. 215.5. THE |
| | GENERATOR HAS A RATED OUTPUT OF 52.5 |
| | AMPS PER SPEC'S. THE CALCULATION |
| | REQUIRED IS FOR THE CIRCUITS IN THE 16 |
| | CIRCUIT GENERATOR PANEL. 702.5 CAPACITY |
| | AND RATING. |
| | AN OPTIONAL STANDBY SYSTEM SHALL HAVE |
| | ADEQUATE CAPACITY AND RATING FOR THE |
| | SUPPLY OF ALL EQUIPMENT INTENDED TO BE |
| | OPERATED AT ONE TIME. OPTIONAL STANDBY |
| | SYSTEM EQUIPMENT SHALL BE SUITABLE FOR |
| | THE MAXIMUM AVAILABLE FAULT CURRENT AT |
| | ITS TERMINALS. THE USER OF THE OPTIONAL |
| | STANDBY SYSTEM SHALL BE PERMITTED TO |
| | SELECT THE LOAD CONNECTED TO THE SYSTEM. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |